Service settings manual
40
Para-
meter
Function
Parameter description
Setting range
Default
value
F1.19
MIN/MAX TEMPERATU-
RE LIMITATION
Setting if controller should respect min. and max. tempe-
rature limitations of certain sensor by control of output.
This function is usefull by thermostatic operation of
output, where min. and max. temperature limitations of
particular sensor should also be respected.
0- NO
1- MIN OFF
2- MAX ON
3- MIN OFF & MAX ON
4- MIN ON
5- MAX OFF
6- MIN ON & MAX OFF
0
F1.20
SENSOR FOR MIN/MAX
TEMPERATURE LIMI-
TATION
Selection of sensor for the MIN/MAX limitation.
1- T1 5- T5
2- T2 6- T6
3- T3 7- T7
4- T4
5*
Table with description of parameters :
Para-
meter
Function
Parameter description
Setting range
Default
value
F2.1
OUTPUT PROGRAM-
MING
Selection of output for programming.
0- NO 4- R4
1- R1 5- R5
2- R2 6- R6
3- R3
0*
F2.2
DEPENDENCE TO
OTHER OUTPUTS
Define dependence of programmed output to other
controller's outputs.
&- selected relay has to be switched-on for programmed
output to be able to switch- on
&!- selected relay has to be switched-off for programmed
output to be able to switch- on
I- programmed output will switch-on always when se-
lected relay is switched-on
I!- programmed output will always switch- on when the
selected relay is switched-off
0- NO
1- &
2- &!
3- I
4- I!
0
F2.3
DEPENDENT OUTPUT Selection of output on which depends operation of
programmed output.
1- R1 4– R4
2- R2 5– R5
3- R3 6– R6
*
F2.4
TIME PROGRAM FOR
OUTPUT
Selection of required time program for programmed
output.
0- NO
1- P1
2- P2
3- P3
4- P4
5- SEL. PROG. TIMER
0
F2.5
THERMOSTATIC OPE-
RATION OF OUTPUT
Selection if programmed output operates as a thermostat. 0- NO
1- YES
2- YES, INVERTED
3- YES, AUX. SOURCE
4- YES, CASC. SOURCE
0
F2.6
TYPE OF AUXILIARY
HEAT SOURCE
Selection of type of heating source.
1- BURNER
2- EL. HEATER
3- HEAT PUMP
0
* Depends on the controller model.
Содержание SGC36
Страница 2: ......
Страница 3: ...Differential controllers SGC36 SGC36HV SGC67 SGC67HV Differenzregler SGC36 SGC36HV SGC67 SGC67HV...
Страница 4: ......
Страница 137: ...137 TABLE 1 Factory settings of parameters P1 TABELLE 1 Werkseinstellungen vom Parametern P1...
Страница 138: ...138 TABLE 2 Factory settings of parameters P2 TABELLE 2 Werkseinstellungen vom Parametern P2...
Страница 139: ...139 TABLE 3 Factory settings of parameters P3 TABELLE 3 Werkseinstellungen vom Parametern P3...
Страница 141: ...NOTES NOTIZEN 141...
Страница 142: ...NOTES NOTIZEN 142...
Страница 143: ......