![Seltron SGC36 Скачать руководство пользователя страница 38](http://html1.mh-extra.com/html/seltron/sgc36/sgc36_manual_1237169038.webp)
Service settings manual
38
Table with description of parameters :
Para-
meter
Function
Parameter description
Setting range
Default
value
F1.1
OUTPUT PROGRAM-
MING
Selection of output for programming.
0- NO 4- R4
1- R1 5- R5
2- R2 6- R6
3- R3
0*
F1.2
DEPENDENCE TO
OTHER OUTPUTS
Define dependence of programmed output to other control-
ler's outputs.
&- selected relay has to be switched-on for programmed
output to be able to switch- on
&!- selected relay has to be switched-off for programmed
output to be able to switch- on
I- programmed output will switch-on always when selected
relay is switched-on
I!- programmed output will always switch- on when the
selected relay is switched-off
0- NO
1- &
2- &!
3- I
4- I!
0
F1.3
DEPENDENT OUTPUT Selection of output on which depends operation of pro-
grammed output.
1- R1 4– R4
2- R2 5– R5
3- R3 6– R6
*
F1.4
TIME PROGRAM FOR
OUTPUT
Selection of required time program for programmed output. 0- NO
1- P1
2- P2
3- P3
4- P4
5- SEL. PROG. TIMER
0
F1.5
THERMOSTATIC
OPERATION OF
OUTPUT
Selection if programmed output operates as a thermostat. 0- NO
1- YES
2- YES, INVERTED
3- YES, AUX. SOURCE
4- YES, CASC. SOURCE
0
F1.6
TYPE OF AUXILIARY
HEAT SOURCE
Selection of type of heating source.
1- BURNER
2- EL. HEATER
3- HEAT PUMP
0
F1.7
SENSOR FOR THER-
MOSTATIC OPERATI-
ON
Selection of sensor for thermostatic operation.
1- T1 2- T2
3- T3 4- T4
5- T5 6- T6
4*
F1.8
THERMOSTAT
HYSTERESIS
Hysteresis for thermostatic operation.
1 ÷ 30 °C
4
F1.9
AUXILIARY HEAT
SOURCE - DELAYED
ACTIVATION
Selection if auxiliary heat source should activate immedia-
tely or with delay if the collectors have trend and tendency
to warm the water to requested temperature. Delay time is
considered as a time in which the collectors should warm
the water to requested temperature. Auxiliary heat source
will activate immediately if collectors don't have trend and
tendency to warm the water to requested temperature in
setted delayed activation time.
0- NO DELAY
1 ÷ 1440 min- DELAY
0
F1.10
AUXILIARY HEAT
SOURCE - STANDBY
AT MIN. TEMPERATU-
RE
Selection if auxiliary heat source should permanently heat
the water to min. temperature.
0- NO
1- YES, BY TIME PR.
2- ALWAYS
0
* Depends on the controller model.
Содержание SGC36
Страница 2: ......
Страница 3: ...Differential controllers SGC36 SGC36HV SGC67 SGC67HV Differenzregler SGC36 SGC36HV SGC67 SGC67HV...
Страница 4: ......
Страница 137: ...137 TABLE 1 Factory settings of parameters P1 TABELLE 1 Werkseinstellungen vom Parametern P1...
Страница 138: ...138 TABLE 2 Factory settings of parameters P2 TABELLE 2 Werkseinstellungen vom Parametern P2...
Страница 139: ...139 TABLE 3 Factory settings of parameters P3 TABELLE 3 Werkseinstellungen vom Parametern P3...
Страница 141: ...NOTES NOTIZEN 141...
Страница 142: ...NOTES NOTIZEN 142...
Страница 143: ......