14
500-33530, Rev B
NOTE 1:
It is recommended that the conduit be installed on the top and
bottom of the enclosure box for wiring and the battery be
installed horizontally.
NOTE 2:
These products are intended to be installed with conduit
fittings in the field. Connections should be used that are
compatible with the Type 1 rated enclosure.
6. ENSURE wire conduit is connected to the junction box with strain
relief.
NOTE 1:
The battery may be oriented in the junction box either vertically
or horizontally as long as the connection wires from the battery
and power supply module have a clear pathway to the
attached wire conduits.
NOTE 2:
If the included battery/battery-type is not used, fish paper must
be used to provide insulation for the installed battery.
7. INSTALL the battery into the junction box.
8. (Optional) REMOVE the power supply module from the cover to
ease in connection of wiring.
NOTE:
Wiring must be Class 1.
9. CONNECT the access control device, access control panel, fire
alarm interface, battery, and lock wiring to the power supply module
terminals.
10. (Optional) INSTALL the power supply module back into the cover,
ensuring the LEDs are facing out at the top right, and SECURE with
the two installation screws.