500-33530, Rev B
Mechanical
Parameter Value
Enclosure
Polycarbonate, UL294 Level 1
Enclosure dimensions
4 1/8” X 4 1/8” X 3 13/16”
AC input wiring
3-wire with strain relief
DC1, LOCK, BAT, FAI, ACC wiring
10-position terminal strip
Electrical
Parameter Value
Input Voltage Range
100–240 VAC, ±10%
Input Frequency
50–60 Hz
Input Surge Resistance
6000 Vpk
Access Control Input
Dry Contact, NO or NC; 32
VDC, 0.02A minimum
Fire Alarm Interface Input
Dry Contact, NO or NC; 32
VDC, 0.02A minimum
Hi-Pot Test
2500 VAC or 3535 VDC
Leakage Current
< 0.5 mA
Output Voltage at No Load
Set to 14.0 VDC, ± 0.2%
Number of Outputs
Two (2) Outputs:
DC1 (Reader): 12 VDC nominal
(9.4–14.6 VDC for compatibility)
LOCK: 12 VDC nominal (9.4–
14.6 VDC for compatibility)
If the battery is discharged
below 9.4V, the lock output is
de-energized
Total Peak Output Current
0.5A (Total current from both
outputs for at least 1 second)
Total Continuous Output Current
0.1A (Total continuous current
from both outputs)
Charging Current (BAT)
12 VDC nominal, 0.1A
maximum continuous, 0.34A
peak (< 2 seconds)
Standby Power
< 20 mW at 230V, < 10mW
at115V
Load Regulation
< 2.5% at 100 mA
Line Regulation
< 0.2%