1.01 Programming the number of stops
DG0
DG1
DG2
DG3
DG4
DG5
DG6
1 0 1
0 0
DG34
[1.01.0]
N
UMBER
OF
STOPS
02
24
From 2 to 24 stops
1.02 Programming the main floor and the parking floor
DG0
DG1
DG2
DG3
DG4
DG5
DG6
1 0 2
DG34
[1.02.0]
M
AIN
FLOOR
01
24
Floor number, 01 is the lowest floor
DG56
[1.02.1]
P
ARKING
FLOOR
OR
PREFERENTIAL
OPERATION
FLOOR
01
24
Floor number, 01 is the lowest floor
For enabling the automatic recall to the parking floor, see timer
1.03 Evacuation floor in case of fire / firefighter access floor
With these parameters you can program the evacuation floors required by EN81-73 standard, or the
firefighter access floor required by EN81-72. First and second evacuation floors are the floors to which the lift
is recalled after an activation of
or
, respectively.
DG0
DG1
DG2
DG3
DG4
DG5
DG6
1 0 3
DG34
[1.03.0]
1
ST
EVACUATION
FLOOR
IN
CASE
OF
FIRE
(EN81-73) / F
IREFIGHTER
ACCESS
FLOOR
(EN81-72)
01
24
Floor number, 01 is the lowest floor
DG56
[1.03.1]
2
ND
EVACUATION
FLOOR
IN
CASE
OF
FIRE
(EN81.73)
01
24
Floor number, 01 is the lowest floor