8
2012.03 / e
LEROY-SOMER
Installation and maintenance
R 450
AVRs
4531 en -
3 - TECHNICAL CHARACTERISTICS
3.1 - Electrical characteristics
- maximum power supply: 150V - 50/60 Hz
- Rated overload current: 10 A - 10 s
- Electronic protection:
- In the case of a short-circuit, the excitation
current is reduced to a value less than 1A
after 10 s
- In the event of loss of voltage reference,
the excitation current is reduced to a value
less than 1A after 1s for AREP/SHUNT, 10 s
for PMG.
- In the event of overexcitation, the current
is reduced as indicated in the next diagram
(see 3.2.1.4).
- Fuses: F1 on X1 and F2 on Z2 10A, 250V.
- Voltage sensing
• 0-110 V terminals = 95 to 140 V
• 0-220 V terminals = 170 to 260 V
• 0-380 V terminals = 340 to 528 V
For other voltages, a transformer should be
used.
- Voltage regulation:± 0.5%.
- Current sensing: (parallel operation): input
S1, S2 intended for 1 C.T. < 2.5 VA cl1,
secondary 1 A or 5 A.
3.2 - Configurations:
3.2.1 - Settings
3.2.1.1 - Voltage
Voltage adjustment via potentiometer
P1
in
the ranges described in the table below:
For 50 and 60 Hz
Max.
High range
320V < Un ≤ 530 V
Low range
80 V ≤ Un ≤ 320 V
WARNING
The allowed adjustment range is
±
5%;
when the setting exceeds these limits,
please check that it is conform with the
power table.
3.2.1.2 - Quadrature droop:
Quadrature
droop
adjustment
via
potentiometer
P4
within a range :
- from 0 to 8% with a PF=0.8 for 400V
applications.
- From 0 to 14% with a PF=0.8 for 240V
applications.
- From 0 to 8% for 110V applications with a
step-up transformer (ratio of 4) placed on
the voltage reference.
The potentiometer
P4
has a non linear
response. Then, when a 1A secondary CT is
connected the effective range starts from
the the second 1/3 of
P4
range and in the
case of a 5A secondary CT the effective
range starts from the first 1/3.
When a 5A CT is used, the adjustment range
is higher, so
P4
must be set to the first 1/4
(anti-clockwise) and then progressively
increase it.
WARNING
The CT must be connected.
3.2.1.3 - Stability:
Stability adjustment via potentiometer
P2.
Selection of rotating switch according to the
machine type and the response time as
indicated in paragraph 3.2.3.
3.2.1.4 - Excitation limitation:
Excitation limitation adjustment via
potentiometer
P3
as described below.
The excitation current limitation threshold in
steady state is set by a potentiometer at
110% of the rated value. The adjustment is
made by the operator during the on-load test
at rated power by tuning the potentiometer.
When the excitation current exceeds this
value, a counter is activated at the speed of
one record per second for 90 s. When this
time is elapsed, the current is reduced to the
value of the rated excitation current. If in the
meantime the excitation current drops
below the threshold value, the counter
counts down at the same speed.
268/297
Содержание R570U
Страница 1: ...User and maintenance manual for generating sets R570U 33504081501NE_1_1 ...
Страница 15: ...Alternator Cabinet Figure 1 3 Examples of identification plates 13 297 ...
Страница 18: ...Sockets voltage 208 120V 16 297 ...
Страница 32: ...Figure 4 3 Braking transmission Figure 4 4 Cross bar fitting Figure 4 5 Tandem bearing fitting 30 297 ...
Страница 125: ...9 Appendix 9 1 Appendix A Engine user and maintenance manual 123 297 ...
Страница 126: ...124 297 ...
Страница 128: ...126 297 ...
Страница 129: ...OPERATOR S MANUAL Generating set and industrial engines 16 liter EMS 2 127 297 ...
Страница 159: ...157 297 ...
Страница 218: ...216 297 ...
Страница 220: ...218 297 ...
Страница 221: ... 2011 AB VOLVO PENTA Volvo reserves the right to make changes Printed on environmentally friendly paper 219 297 ...
Страница 222: ...7748681 English 12 2011 220 297 ...
Страница 223: ...9 2 Appendix B Alternator user and maintenance manual 221 297 ...
Страница 224: ...222 297 ...
Страница 226: ...224 297 ...
Страница 249: ...23 LEROY SOMER 2011 03 g Installation and maintenance LSA 47 2 4 POLES ALTERNATORS 3742 en 247 297 ...
Страница 250: ...www leroy somer com 248 297 ...
Страница 261: ...Installation and maintenance R250 A V R 4067 en 2009 05 b LEROY SOMER 11 259 297 ...
Страница 281: ...2012 03 e LEROY SOMER 19 Installation and maintenance R 450 AVRs 4531 en 279 297 ...
Страница 282: ...www leroy somer com 280 297 ...