3.4. Electricity
a) Connections - general information
As with low voltage electrical installations, use and maintenance is governed by standard NFC 15.100 (France) or by the standards in
the relevant country, based on international standard IEC 60364-6-61.
They must also adhere to the regulations in the NFC 15.401 application guide (France) or to the regulations and standards in the
relevant country.
b) Power cables
These can be unipolar or multipolar according to the power of the generating set.
Power cables should preferably be installed in ducts or on a cable tray for this purpose.
The cable cross-section and number of cables should be determined according to the cable type and the current standards to be
observed in the country of installation. The choice of conductors must comply with international standard
IEC 30364-5-52.
Three phase - Calculation hypothesis
Fitting method = wiring in cable runs or non perforated trays.
Permissible voltage drop = 5%
Multiconductors or single conductor joined when precision 4X…(1)
Cable type PVC 70°C (e.g. H07RNF).
Ambient temperature = 30°C.
Circuit breaker
calibre
(A)
Cable sizes
0 - 50m
51 - 100m
101 - 150m
mm²/AWG
mm²/AWG
mm²/AWG
10
1.5 / 14
2.5 / 12
4 / 10
16
2.5 / 12
4 / 10
6 / 9
20
2.5 / 12
4 / 10
6 / 9
25
4 / 10
6 / 9
10 / 7
32
6 / 9
6 / 9
10 / 7
40
10 / 7
10 / 7
16 / 5
50
10 / 7
10 / 7
16 / 5
63
16 / 5
16 / 5
25 / 3
80
25 / 3
25 / 3
35 / 2
100
35 / 2
35 / 2
4X(1X50) / 0
125
(1)
4X(1X50) / 0
4X(1X50) / 0
4X(1X70) / 2/0
160
(1)
4X(1X70) / 2/0
4X(1X70) / 2/0
4X(1X95) / 4/0
250
(1)
4X(1X95) / 4/0
4X(1X150) / 2350MCM
4X(1X150) / 2350MCM
400
(1)
4X(1X185) / 0400MCM
4X(1X185) / 0400MCM
4X(1X185) / 0400MCM
630
(1)
4X(2X1X150) / 2x 2350MCM
4X(2X1X150) / 2x 2350MCM
4X(2X1X150) / 2x 2350MCM
Single phase - Calculation hypothesis
Fitting method = wiring in cable runs or non perforated trays.
Permissible voltage drop = 5%
Multiconductors.
Cable type PVC 70°C (e.g. H07RNF).
Ambient temperature = 30°C.
Circuit breaker
rating (A)
Cable sizes
0 - 50m
51 - 100m
101 - 150m
mm²/AWG mm²/AWG
mm²/AWG
10
4 / 10
10 / 7
10 / 7
16
6 / 9
10 / 7
16 / 5
20
10 / 7
16 / 5
25 / 3
25
10 / 7
16 / 5
25 / 3
32
10 / 7
25 / 3
35 / 2
40
16 / 5
35 / 2
50 / 0
50
16 / 5
35 / 2
50 / 0
63
25 / 3
50 / 0
70 / 2/0
80
35 / 2
50 / 0
95 / 4/0
100
35 / 2
70 / 2/0
95 / 4/0
125
50 / 0
95 / 4/0
120 / 2250MCM
c) Battery cables
Install the battery or batteries in the immediate vicinity of the electric starter motor. The cables will be connected directly from the
battery terminals to the starter motor terminals.
The primary instruction to follow is to ensure that the polarities between the battery and starter motor match. Never reverse the positive
and negative battery terminals when connecting them. This could cause severe damage to the electrical equipment.
The minimum cross-section of the cables will be 70 mm
2
. It varies according to the power of the starter motor but also the distance
between the batteries and the set (voltage drops on the line).
25/297
Содержание R570U
Страница 1: ...User and maintenance manual for generating sets R570U 33504081501NE_1_1 ...
Страница 15: ...Alternator Cabinet Figure 1 3 Examples of identification plates 13 297 ...
Страница 18: ...Sockets voltage 208 120V 16 297 ...
Страница 32: ...Figure 4 3 Braking transmission Figure 4 4 Cross bar fitting Figure 4 5 Tandem bearing fitting 30 297 ...
Страница 125: ...9 Appendix 9 1 Appendix A Engine user and maintenance manual 123 297 ...
Страница 126: ...124 297 ...
Страница 128: ...126 297 ...
Страница 129: ...OPERATOR S MANUAL Generating set and industrial engines 16 liter EMS 2 127 297 ...
Страница 159: ...157 297 ...
Страница 218: ...216 297 ...
Страница 220: ...218 297 ...
Страница 221: ... 2011 AB VOLVO PENTA Volvo reserves the right to make changes Printed on environmentally friendly paper 219 297 ...
Страница 222: ...7748681 English 12 2011 220 297 ...
Страница 223: ...9 2 Appendix B Alternator user and maintenance manual 221 297 ...
Страница 224: ...222 297 ...
Страница 226: ...224 297 ...
Страница 249: ...23 LEROY SOMER 2011 03 g Installation and maintenance LSA 47 2 4 POLES ALTERNATORS 3742 en 247 297 ...
Страница 250: ...www leroy somer com 248 297 ...
Страница 261: ...Installation and maintenance R250 A V R 4067 en 2009 05 b LEROY SOMER 11 259 297 ...
Страница 281: ...2012 03 e LEROY SOMER 19 Installation and maintenance R 450 AVRs 4531 en 279 297 ...
Страница 282: ...www leroy somer com 280 297 ...