Installation and maintenance
LSA 47.2 - 4 POLES
ALTERNATORS
3742 en -
3.3.4 - Connection checks
Electrical installations must comply with
the current legislation in force in the
country of use.
Check that:
- The residual circuit-breaker conforms to
legislation on protection of personnel, in
force in the country of use, and has been
correctly installed on the alternator power
output as close as possible to the alternator.
(In this case, disconnect the wire of the
interference suppression module linking the
neutral).
- Any protection devices in place have not
been tripped.
- If there is an external AVR, the connections
between the alternator and the cabinet are
made in accordance with the connection
diagram.
- There is no short-circuit phase-phase or
phase-neutral between the alternator output
terminals and the generator set control
cabinet (part of the circuit not protected by
circuitbreakers or relays in the cabinet).
- The machine should be connected with the
busbar separating the terminals as shown in
the terminal connection diagram.
3.4 - Commissioning
The machine can only be started up and
used if the installation is in accordance
with the regulations and instructions
defined in this manual.
The machine is tested and set up at the
factory. When first used with no load, make
sure that the drive speed is correct and
stable (see the nameplate). With the
regreasable bearing option, we recommend
greasing the bearings at the time of
commissioning (see 4.2.2).
On application of the load, the machine
should achieve its rated speed and voltage;
however, in the event of abnormal operation,
the machine setting can be altered (follow
the adjustment procedure in section 3.5). If
the machine still operates incorrectly, the
cause of the malfunction must be located
(see section 4.4).
3.5 - Setting up
The various adjustments during tests
must be made by a qualified engineer.
Ensure that the drive speed specified on
the nameplate is reached before
commencing adjustment.
After operational testing, replace all
access panels or covers.
The AVR is used to make any adjustments
to the machine.
234/297
Содержание R570U
Страница 1: ...User and maintenance manual for generating sets R570U 33504081501NE_1_1 ...
Страница 15: ...Alternator Cabinet Figure 1 3 Examples of identification plates 13 297 ...
Страница 18: ...Sockets voltage 208 120V 16 297 ...
Страница 32: ...Figure 4 3 Braking transmission Figure 4 4 Cross bar fitting Figure 4 5 Tandem bearing fitting 30 297 ...
Страница 125: ...9 Appendix 9 1 Appendix A Engine user and maintenance manual 123 297 ...
Страница 126: ...124 297 ...
Страница 128: ...126 297 ...
Страница 129: ...OPERATOR S MANUAL Generating set and industrial engines 16 liter EMS 2 127 297 ...
Страница 159: ...157 297 ...
Страница 218: ...216 297 ...
Страница 220: ...218 297 ...
Страница 221: ... 2011 AB VOLVO PENTA Volvo reserves the right to make changes Printed on environmentally friendly paper 219 297 ...
Страница 222: ...7748681 English 12 2011 220 297 ...
Страница 223: ...9 2 Appendix B Alternator user and maintenance manual 221 297 ...
Страница 224: ...222 297 ...
Страница 226: ...224 297 ...
Страница 249: ...23 LEROY SOMER 2011 03 g Installation and maintenance LSA 47 2 4 POLES ALTERNATORS 3742 en 247 297 ...
Страница 250: ...www leroy somer com 248 297 ...
Страница 261: ...Installation and maintenance R250 A V R 4067 en 2009 05 b LEROY SOMER 11 259 297 ...
Страница 281: ...2012 03 e LEROY SOMER 19 Installation and maintenance R 450 AVRs 4531 en 279 297 ...
Страница 282: ...www leroy somer com 280 297 ...