Scheduled to acquire
UL Standards
Specifications
Model
HRLE090-W-40
Cooling method
Water-cooled refrigeration
Refrigerant
R410A (HFC)
Refrigerant charge
kg
1.9
Control method
PID control
Ambient temperature
°
C
2 to 45
Cir
culating fluid system
Circulating fluid
*
1
Tap water, Deionized (pure) water
Set temperature range
°
C
CH1: 15 to 25, CH2: CH1 + 0 to 15
Cooling capacity (CH1, 2 total) 50/60 Hz
*
2
kW
9.5/11.0
Heating capacity (CH1, 2 total) 50/60 Hz
*
3
kW
2.0/2.5
Temperature stability
*
4
°
C
CH1:
±
0.1, CH2:
±
0.5
Pump
capacity
Rated flow 50/60 Hz
*
5
L/min
CH1: 25/35, CH2: 2/2
Max. flow rate 50/60 Hz
L/min
55/65
Max. pump head
m
50
Min. operating flow rate 50/60 Hz
*
6
L/min
CH1: 25/35, CH2: 1/1
Tank capacity (CH1, 2 total)
L
Approx. 18
Circulating fluid outlet, Circulating fluid return port
CH1: Rc1, CH2: Rc1/2
Tank drain port
Rc1/4
Fluid contact material
Stainless steel, Copper (Heat exchanger brazing), Bronze (Pump),
Ceramic, Carbon, FKM, PP, PE, POM, PVC, PA, EPDM
Facility water system
Temperature range
°
C
5 to 40
Pressure range
MPa
0.3 to 0.5
Required flow 50/60 Hz
L/min
25/25
Facility water pressure differential
MPa
0.3 or more
Facility water inlet/outlet
Rc1/2
Fluid contact material
Stainless steel, Copper (Heat exchanger brazing), Brass, PTFE, NBR, EPDM
Electrical system
Power supply
3-phase 380 to 415 VAC (50/60 Hz)
Allowable voltage range
±
10% (No continuous voltage fluctuation)
3-phase 460 to 480 VAC (60 Hz)
Allowable voltage range +4%, −10% (Max. voltage less than 500 V and no continuous voltage fluctuation)
Applicable earth
leakage breaker
*
8
Rated current
A
20
Sensitivity current
mA
30
Rated operating current 50/60 Hz
A
6.7/7.1
Rated power consumption 50/60 Hz
kW(kVA)
3.5/4.4 (4.7/5.0)
Communication function
Contact input/output, Serial communication (RS-485)
Noise level
dB(A)
65
Accessories
*
7
Operation Manual (for installation/operation) 2 copies (English 1 pc./Japanese 1 pc.),
Anchor bolt fixing brackets 2 pcs., Cable accessory 1 pc. (For communication cable)
Weight
kg
134
*
1 Use fluid that fulfills the conditions below as the circulating fluid.
Tap water: Standard of The Japan Refrigeration And Air Conditioning Industry Association (JRA GL-02-1994)
Deionized (pure) water: Electric conductivity 0.4
μ
S/cm or higher (Electric resistivity 2.5 M
Ω
·cm or lower)
*
2
q
Facility water temperature: 32
°
C,
w
Circulating fluid: Tap water,
e
Circulating fluid temperature: CH1 20
°
C/CH2 25
°
C,
r
Circulating fluid flow rate: Rated flow,
t
Power supply: 400 VAC
*
3
q
Facility water temperature: 32
°
C,
w
Circulating fluid: Tap water,
e
Circulating fluid flow rate: Rated flow,
r
Power supply: 400 VAC
*
4
q
Facility water temperature: 32
°
C,
w
Circulating fluid: Tap water,
e
Circulating fluid temperature: CH1 20
°
C/CH2 25
°
C,
r
Circulating fluid flow rate:
Rated flow,
t
Power supply: 400 VAC,
y
Piping length: Shortest,
u
Load: Same as the cooling capacity
*
5 Circulating fluid discharge pressure = at 0.5 MPa
*
6 Fluid flow rate to maintain the cooling capacity and to keep the circulating fluid discharge pressure at 0.5 MPa or less
If the actual flow rate is lower than this, install bypass piping.
*
7 The anchor bolt fixing brackets are used for securing the product to wooden skids when packaging the thermo-chiller.
The anchor bolts are not attached.
*
8 To be prepared by the customer
Water-cooled refrigeration
How to Order
HRLE
W 40
Power supply
40
3-phase 380 to 415 VAC (50/60 Hz)
3-phase 460 to 480 VAC (60 Hz)
Cooling capacity
CH1, 2 total
090
9.5 kW
090
Option
Nil
None
C
With inverter for compressor
M
Deionized water (Pure water) piping
P
With inverter for pump
Cooling method
W
Water-cooled refrigeration
3-phase 380 to 415 VAC (50/60 Hz)
3-phase 460 to 480 VAC (60 Hz)
Power
supply
¡
When multiple options are combined, indicate
the symbols in alphabetical order.
Water-cooled refrigeration
12
Thermo-chiller
Compact Dual/Basic Type for Lasers
HRLE
Series