e
Electric Conductivity Control Set
This set can be used to display and control the electric conductivity of the circulating fluid. Refer to the Operation Manual for
details.
Part no.
Applicable model
HRL-DI001
HRLE090-
m
-
m
Measurement range of electric conductivity 2.0 to 48.0
µ
S/cm
Set range of target electric conductivity 0.5 to 45.0
µ
S/cm
Set range of electric
conductivity hysteresis
0.1 to 10.0
µ
S/cm
Operating temperature range
(Circulating fluid temperature)
5 to 60
°
C
Power consumption
400 mA or less
(197)
(170)
Mounting dimensions
CH1 Circulating
fluid return port
CH2 Circulating
fluid return port
CH2 Circulating
fluid outlet
CH1 Circulating
fluid outlet
DI filter
x 4
e
o
i
r
!0
!1
w
u
y
t
!4
!6
!2
!3
!5
r
t
q
Parts List
No.
Description
Fluid contact material
Qty.
q
DI filter cartridge
(Part no.: HRR-DF001)
∗
1
PP, PE
1
w
DI filter inlet fitting assembly
Stainless steel, PA
1
e
DI filter outlet fitting assembly
Stainless steel, PA
1
r
O-ring
EPDM
2
t
Clip
—
2
y
Nipple (Size: 1 inch)
Stainless steel
2
u
Union (Size: 1 inch)
Stainless steel
1
i
DI control piping assembly
Stainless steel
1
o
Nipple (Size: 1/2 inch)
Stainless steel
2
!0
Union (Size: 1/2 inch)
Stainless steel
1
!1
DI sensor piping assembly
Stainless steel
1
!2
Mounting bracket
—
1
!3
DI filter inlet hose
PVC
1
!4
DI filter outlet hose
PVC
1
!5
Hose clamp
—
4
!6
Mounting screw (Size: M5)
—
2
!7
Cable tie holder
—
5
!8
Binding band
—
4
!9
Reusable band
—
1
@0
Sealant tape
PTFE
1
@1
DI control solenoid valve extension cable
—
1
∗
1 The product should be replaced when it can no longer preserve the
electrical conductivity set value.
21
HRLE
Series