0
10
20
30
40
50
60
70
Circulating fluid flow rate [L/min]
Circulating fluid pressure [MPa]
0.5
0.4
0.3
0.2
0.1
0
50 Hz
Usable
range
60 Hz
Usable
range
50 Hz
60 Hz
Return port
15
20
25
Circulating fluid temperature [
°
C]
Cooling capacity [kW]
12
10
8
6
4
2
0
Ambient temperature 32
°
C
Ambient temperature 45
°
C
Ambient temperature 40
°
C
15
20
25
Circulating fluid temperature [
°
C]
Cooling capacity [kW]
12
10
8
6
4
2
0
Ambient temperature 32
°
C
Ambient temperature 45
°
C
Ambient temperature 40
°
C
15
20
25
Circulating fluid temperature [
°
C]
Cooling capacity [kW]
12
10
8
6
4
2
0
Facility water temperature 32
°
C
Facility water temperature 40
°
C
15
20
25
Circulating fluid temperature [
°
C]
Cooling capacity [kW]
14
12
10
8
6
4
2
0
Facility water temperature 32
°
C
Facility water temperature 40
°
C
HRLE090-A-20/40
HRLE090-A-20/40
HRLE090-
m
-20/40
Cooling Capacity
Pump Capacity
[50 Hz]
[60 Hz]
*
The pump capacity is the capacity of CH1 when 2 L/min are applied
to CH2.
*
The cooling capacity is the sum of the capacities of CH1 and CH2.
*
The ambient temperature of 32
°
C is at 60% fan output (default setting).
*
The ambient temperatures of 40
°
C and 45
°
C are at 100% fan output. (The noise level rises by approx. 3 dB(A) from the rated condition.)
Mechanical Seal Pump
The pump used for the thermo-chiller HRLE090 series uses a
mechanical seal with the fixed ring and rotary ring used for the
shaft seal part. If foreign matter enter the gap between the
seals, this may cause a trouble such as leakage from the seal
part or pump lock. Therefore, it is strongly recommended to
install the particle filter in the return piping of the chiller.
Caution
Mechanical seal pump
Mechanical seal
Casing
Mechanical
seal
Shaft
Impeller
HRLE090-W-20/40
HRLE090-W-20/40
[50 Hz]
[60 Hz]
*
The cooling capacity is the sum of the capacities of CH1 and CH2.
13
HRLE
Series
Compact Dual/Basic Type for Lasers