4.15
Date Code 20020903
SEL-587Z Instruction Manual
Control Logic
SEL
OGIC
Control Equation Variables/Timers
EXAMPLE 4.8
Transformer Settings Example
When the SEL-587Z is used as transformer protection, configure a
dedicated breaker failure protection element as follows (see
SV6 =
TR1*50P1
SEL
OGIC
Variable SV6
SV7 =
TR1*50P1
SEL
OGIC
Variable SV7
Retrip:
OUT1 =
SV6T
Output Contact OUT1
Breaker failure trip:
OUT2 =
SV7T
Output Contact OUT2
Figure 4.6
Breaker Failure Function Created
With SEL
OGIC
Control Equation Variables/Timers.
TR1 functions as a breaker failure initiate input. Phase instantaneous
overcurrent element 50P1 functions as the fault detector.
Timer pickup setting SV6PU provides retrip delay, if desired (can be
set to zero).
Timer pickup setting SV7PU provides breaker failure timing. Timer
dropout setting SV7DO holds the breaker failure trip output (output
contact OUT2) closed for extra time if needed after the breaker
failure logic unlatches (fault detector 50P1 or TR1 drops out).
TR1
50P1
SV7T
SV7
SV6
SV6T
SV6PU
SV6DO
SV7PU
SV7DO
OUT1
(Retrip)
OUT2
(Breaker
Failure
Trip)
Содержание SEL-587Z
Страница 10: ...This page intentionally left blank ...
Страница 12: ...This page intentionally left blank ...
Страница 66: ...This page intentionally left blank ...
Страница 106: ...This page intentionally left blank ...
Страница 126: ...This page intentionally left blank ...
Страница 162: ...This page intentionally left blank ...
Страница 228: ...This page intentionally left blank ...
Страница 260: ...This page intentionally left blank ...
Страница 276: ...This page intentionally left blank ...