B.7
Date Code 20020903
SEL-587Z Instruction Manual
Firmware Upgrade Instructions
Start SEL
BOOT
settings in case you need to reenter settings. If you have SEL-5010 Relay
Assistant Software available for your relay, use this software to record existing
relay settings and proceed to
. Otherwise, perform
the following steps.
Step 1. From the Transfer menu in HyperTerminal, select Capture Text.
Step 2. Enter a directory and file name for a text file where you will
record existing relay settings.
Step 3. Click
Start
.
The
Capture Text
command copies all the information you
retrieve and all the key strokes you type until you send the
command to stop capturing text. The terminal emulation
program stores these data in the text file.
Step 4. Type
SHO C<Enter>
to retrieve the relay calibration settings.
If you do not already have copies of the Relay, Logic, Port,
Text, and SER settings, use the following
SHOW
commands to
retrieve the necessary settings:
SHO
,
SHO L
,
SHO P 1
,
SHO P F
,
SHO T
, and
SHO R
.
Step 5. From the Transfer menu in HyperTerminal, select Capture Text
and click
Stop
.
Step 6. Print the text file you created in
through
Save this file for later reference.
Step 7. Make a written record of the present relay data transmission
setting for later use in the upgrade procedure.
This setting is SPEED in the
SHO P
relay settings output. The
SPEED value should be the same as the value you recorded
earlier in
.
D Start SEL
BOOT
Step 1. Start the relay SEL
BOOT
program.
a. Type
L_D<Enter>
.
The relay responds, “Disable relay to send or receive
firmware (Y/N)?”
b. Type
Y<Enter>
.
The relay responds, “Are you sure (Y/N)?”
c. Type
Y<Enter>
.
The relay responds, “Relay Disabled.”
Step 2. Wait for the SEL
BOOT
program to load.
The front-panel LCD screen displays the SEL
BOOT
-500-Rxxx
firmware number (e.g., “SELboot-500- R100”).
xxx is the SEL
BOOT
revision number and is a different revision
number from the relay firmware revision number.
When finished loading the SEL
BOOT
program, the relay
responds to the terminal with the SEL
BOOT
action prompt !>.
Step 3. Press
<Enter>
to confirm that the relay is in SEL
BOOT
.
You will see another !> SEL
BOOT
action prompt.
Содержание SEL-587Z
Страница 10: ...This page intentionally left blank ...
Страница 12: ...This page intentionally left blank ...
Страница 66: ...This page intentionally left blank ...
Страница 106: ...This page intentionally left blank ...
Страница 126: ...This page intentionally left blank ...
Страница 162: ...This page intentionally left blank ...
Страница 228: ...This page intentionally left blank ...
Страница 260: ...This page intentionally left blank ...
Страница 276: ...This page intentionally left blank ...