B.13
Date Code 20020903
SEL-587Z Instruction Manual
Firmware Upgrade Instructions
Verify Calibration, Status, and Metering
NOTE:
If the relay prompts you to
enter a part number, use either the
number from the label on the disk
containing your firmware or the
number from the new part number
sticker (if supplied).
Step 6. Press
<Enter>
to check for the Access Level 0 action prompt =
indicating that serial communication is successful.
Step 7. Use the
ACC
and
2AC
commands to reenter Access Level 2.
The factory default passwords are in effect; use the default
relay passwords listed in the
PAS
command in
Step 8. Restore original settings.
a. If you have SEL-5010 software, restore original settings
as necessary.
b. If you do not have the SEL-5010 software, restore
original settings by issuing the necessary
SET
commands:
SET
,
SET L
,
SET P 1
,
SET P F
,
SET T
,
and
SET R
.
Step 9. Use the
PAS
command to set the original relay passwords.
Type
PAS 1: Ot3579<Enter>
to set the Access Level 1
password to Ot3579.
Use a similar format for other password levels. The
PAS
command is case sensitive, so the relay treats
lower-case and upper-case letters differently.
Step 10. If any failure status messages still appear on the relay display,
see the
Section 10: Testing and Troubleshooting
. You can also
contact the factory or your Technical Service Center for
assistance.
H Verify Calibration, Status, and Metering
Step 1. Use the
ACC
and
2AC
commands to reenter Access Level 2.
Step 2. Type
SHO C<Enter>
to verify the relay calibration settings.
If the settings do not match the settings contained in the text file
you recorded in
Save Settings and Other Data on page B.6
contact the factory or your Technical Service Center for
assistance.
Step 3. Type
ID<Enter>
to display relay firmware information
including the relay part number. Confirm that the new firmware
revision number appears in the FID string.
Step 4. Reenter Access Level 2 (if necessary).
Step 5. Type
STA<Enter>
to verify that all relay self-test parameters
are within tolerance.
Step 6. Apply current and voltage signals to the relay.
Step 7. Type
MET<Enter>
to verify that the current and voltage
signals are correct.
Step 8. Use the
TRIGGER
(
TRI
) and
EVENT
(
EVE
) commands to
verify that the magnitudes of the current and voltage signals
you applied to the relay match those displayed in the event
report.
Step 9. If these values do not match, check the relay settings and
wiring.
Содержание SEL-587Z
Страница 10: ...This page intentionally left blank ...
Страница 12: ...This page intentionally left blank ...
Страница 66: ...This page intentionally left blank ...
Страница 106: ...This page intentionally left blank ...
Страница 126: ...This page intentionally left blank ...
Страница 162: ...This page intentionally left blank ...
Страница 228: ...This page intentionally left blank ...
Страница 260: ...This page intentionally left blank ...
Страница 276: ...This page intentionally left blank ...