6.13
Date Code 20020903
SEL-587Z Instruction Manual
Serial Port Communications
SEL Binary Protocols, Fast Meter, and Fast Operate
494100000000
Analog channel name (IA)
00
Analog channel type (integer)
01
Scale factor type (float)
0004
Scale factor offset in A5D1 message
494200000000
Analog channel name (IB)
00
Analog channel type (integer)
01
Scale factor type (float)
0004
Scale factor offset in A5D1 message
494300000000
Analog channel name (IC)
00
Analog channel type (integer)
01
Scale factor type (float)
0004
Scale factor offset in A5D1 message
383741000000
Analog channel name (87A)
00
Analog channel type (integer)
01
Scale factor type (float)
0008
Scale factor offset in A5D1 message
383742000000
Analog channel name (87B)
00
Analog channel type (integer)
01
Scale factor type (float)
0008
Scale factor offset in A5D1 message
383743000000
Analog channel name (87C)
00
Analog channel type (integer)
01
Scale factor type (float)
0008
Scale factor offset in A5D1 message
1-byte
Line configuration: 00–ABC, 01–ACB; based on PHROT relay set-
ting
03
Calculation type (currents only)
FFFF
Skew correction offset (none)
FFFF
Rs scale factor offset (none)
FFFF
Xs scale factor offset (none)
00
IA channel index
01
IB channel index
02
IC channel index
FF
VA channel index (none)
FF
VB channel index (none)
FF
VC channel index (none)
00
Reserved
xx
1-byte checksum of all preceding bytes
Table 6.7
A5C1 Fast Meter Configuration Block
(Sheet 2 of 2)
Data
Description
Содержание SEL-587Z
Страница 10: ...This page intentionally left blank ...
Страница 12: ...This page intentionally left blank ...
Страница 66: ...This page intentionally left blank ...
Страница 106: ...This page intentionally left blank ...
Страница 126: ...This page intentionally left blank ...
Страница 162: ...This page intentionally left blank ...
Страница 228: ...This page intentionally left blank ...
Страница 260: ...This page intentionally left blank ...
Страница 276: ...This page intentionally left blank ...