SEL-351-5, -6, -7 Relay
Instruction Manual
Date Code 20070117
Setting the Relay
Relay Word Bits (Used in SEL
OGIC
Control Equations)
5
50A
50A1 + 50A2 + 50A3 + 50A4 (see
)
50B
50B1 + 50B2 + 50B3 + 50B4 (see
)
50C
50C1 + 50C2 + 50C3 + 50C4 (see
)
51A
A-phase current above pickup setting 51AP for A phase
time-overcurrent element 51AT (see
Testing, Control
51AT
A-phase time-overcurrent element 51AT timed out (see
)
Tripping
51AR
A-phase time-overcurrent element 51AT reset (see
Testing
51B
B-phase current above pickup setting 51BP for B phase
time-overcurrent element 51BT (see
Testing, Control
51BT
B-phase time-overcurrent element 51BT timed out (see
)
Tripping
6
51BR
B-phase time-overcurrent element 51BT reset (see
Testing
51C
C-phase current above pickup setting 51CP for C phase
time-overcurrent element 51CT (see
Testing, Control
51CT
C-phase time-overcurrent element 51CT timed out (see
)
Tripping
51CR
C-phase time-overcurrent element 51CT reset (see
Testing
51P
Maximum phase current above pickup setting 51PP for phase
time-overcurrent element 51PT (see
)
Testing, Control
51PT
Phase time-overcurrent element 51PT timed out (see
Tripping
51PR
Phase time-overcurrent element 51PT reset (see
)
Testing
51N
Neutral ground current (channel IN) above pickup setting 51NP for
neutral ground time-overcurrent element 51NT (see
)
Testing, Control
7
51NT
Neutral ground time-overcurrent element 51NT timed out (see
Tripping
51NR
Neutral ground time-overcurrent element 51NT reset (see
)
Testing
51G
Residual ground current above pickup setting 51GP for ground
time-overcurrent element 51GT (see
)
Testing, Control
51GT
Residual ground time-overcurrent element 51GT timed out (see
)
Tripping
51GR
Residual ground time-overcurrent element 51GT reset (see
Testing
51Q
a
Negative-sequence current above pickup setting 51QP for
negative-sequence time-overcurrent element 51QT (see
)
Testing, Control
Negative-sequence time-overcurrent element 51QT timed out (see
Tripping
51QR
Negative-sequence time-overcurrent element 51QT reset (see
)
Testing
Table 9.6
Relay Word Bit Definitions for SEL-5, -6, -7
(Sheet 2 of 18)
Row
Bit
Definition
Primary Application
Содержание SEL-351-5
Страница 10: ...This page intentionally left blank ...
Страница 22: ...This page intentionally left blank ...
Страница 40: ...This page intentionally left blank ...
Страница 80: ...This page intentionally left blank ...
Страница 202: ...This page intentionally left blank ...
Страница 238: ...This page intentionally left blank ...
Страница 320: ...This page intentionally left blank ...
Страница 402: ...This page intentionally left blank ...
Страница 436: ...This page intentionally left blank ...
Страница 478: ...This page intentionally left blank ...
Страница 500: ...This page intentionally left blank ...
Страница 594: ...This page intentionally left blank ...
Страница 598: ...This page intentionally left blank ...
Страница 622: ...This page intentionally left blank ...
Страница 644: ...This page intentionally left blank ...
Страница 674: ...This page intentionally left blank ...
Страница 676: ...This page intentionally left blank ...