1.15
Date Code 20070117
Instruction Manual
SEL-351-5, -6, -7 Relay
Introduction and Specifications
Specifications
Radiated EMI:
IEC 60255-22-3:1989 Electrical relays,
Section 3: Radiated electromagnetic
field disturbance tests, Severity Level
3 (10 V/m)
IEEE C37.90.2-IEEE Trial-Use
Standard, Withstand Capability of
Relay Systems to Radiated
Electromagnetic Interference from
Transceivers, 35 V/m (type test).
Exceptions:
5.5.2(2) Performed with 200
frequency steps per octave.
5.5.3 Digital Equipment Modulation
Test not performed.
5.5.4 Test signal turned off between
frequency steps to simulate keying.
Surge Withstand:
IEC 60255-22-1:1988 Electrical
disturbance tests for measuring relays
and protection equipment, Part 1:
1 MHz burst disturbance tests.
Severity Level 3 (2.5 kV common
mode, 2.5 kV differential)
IEEE C37.90.1-1989
3.0 kV oscillatory; 5.0 kV fast
transient
Vibration and Shock Tests
Shock and Bump:
IEC 60255-21-2:1988 Electrical relays,
Part 21: Vibration, shock, bump, and
seismic tests on measuring relays and
protection equipment, Section Two:
Shock and bump tests, Class 1
IEC 60255-21-3:1993 Electrical relays,
Part 21: Vibration, shock, bump, and
seismic tests on measuring relays and
protection equipment, Section Three:
Seismic tests, Class 2
Sinusoidal Vibration:
IEC 60255-21-1:1988 Electrical relays,
Part 21: Vibration, shock, bump, and
seismic tests on measuring relays and
protection equipment, Section One:
Vibration tests (sinusoidal), Class 1
Certifications
ISO: Relay is designed and manufactured to an ISO-9001 certified
quality program.
UL/CSA: UL recognized to the requirements of
UL-508; CSA
C22.2, N.14 for Industrial Control Equipment
; and
UL-1053,
Ground-Fault Sensing and Relay Equipment
.
CE: CE Mark
Processing Specifications
AC Voltage and Current Inputs
16 samples per power system cycle, 3 dB low-pass filter cut-off
frequency of 560 Hz
Digital Filtering
One cycle cosine after low-pass analog filtering.
Net filtering (analog plus digital) rejects dc and all harmonics
greater than the fundamental.
Protection and Control Processing
4 times per power system cycle
Relay Element Pickup Ranges and Accuracies
Instantaneous/Definite-Time Overcurrent Elements
Pickup Range:
0.25–100.00 A, 0.01 A steps
(5 A nominal)
1.00–170.00 A, 0.01 A steps
(5 A nominal—for phase-to-phase
elements)
0.050–100.000 A, 0.010 A steps
(5 A nominal—for residual ground
elements)
0.05–20.00 A, 0.01 A steps
(1 A nominal)
0.20–34.00 A, 0.01 A steps
(1 A nominal—for phase-to-phase
elements)
0.010–20.000 A, 0.002 A steps
(1 A nominal—for residual ground
elements)
0.005–2.500 A, 0.001 A steps
(0.2 A nominal neutral channel (IN)
current input)
0.005–1.500 A, 0.001 A steps
(0.05 A nominal neutral channel (IN)
current input)
Steady-State
Pickup Accuracy:
±0.05 A and ±3% of setting
(5 A nominal)
±0.01 A and ±3% of setting
(1 A nominal)
±0.001 A and ±3% of setting
(0.2 A nominal neutral channel (IN)
current input)
±0.001 A and ±5% of setting
(0.05 A nominal neutral channel (IN)
current input)
Transient Overreach:
±5% of pickup
Time Delay:
0.00–16,000.00 cycles, 0.25 cycle steps
Timer Accuracy:
±0.25 cycle and ±0.1% of setting
Note:
See pickup and reset time curves in
and
Time-Overcurrent Elements
Pickup Range:
0.25–16.00 A, 0.01 A steps
(5 A nominal)
0.10–16.00 A, 0.01 A steps
(5 A nominal—for residual ground
elements)
0.05–3.20 A, 0.01 A steps
(1 A nominal)
0.02–3.20 A, 0.01 A steps
(1 A nominal—for residual ground
elements)
0.005–0.640 A, 0.001 A steps
(0.2 A nominal neutral channel (IN)
current input)
0.005–0.160 A, 0.001 A steps
(0.05 A nominal neutral channel (IN)
current input)
Steady-State
Pickup Accuracy:
±0.05 A and ±3% of setting
(5 A nominal)
±0.01 A and ±3% of setting
(1 A nominal)
±0.005 A and ±3% of setting
(0.2 A nominal neutral channel (IN)
current input)
±0.001 A and ±5% of setting
(0.05 A nominal neutral channel (IN)
current input)
Time Dial Range:
0.50–15.00, 0.01 steps (US)
0.05–1.00, 0.01 steps (IEC)
Содержание SEL-351-5
Страница 10: ...This page intentionally left blank ...
Страница 22: ...This page intentionally left blank ...
Страница 40: ...This page intentionally left blank ...
Страница 80: ...This page intentionally left blank ...
Страница 202: ...This page intentionally left blank ...
Страница 238: ...This page intentionally left blank ...
Страница 320: ...This page intentionally left blank ...
Страница 402: ...This page intentionally left blank ...
Страница 436: ...This page intentionally left blank ...
Страница 478: ...This page intentionally left blank ...
Страница 500: ...This page intentionally left blank ...
Страница 594: ...This page intentionally left blank ...
Страница 598: ...This page intentionally left blank ...
Страница 622: ...This page intentionally left blank ...
Страница 644: ...This page intentionally left blank ...
Страница 674: ...This page intentionally left blank ...
Страница 676: ...This page intentionally left blank ...