12.41
Date Code 20070117
Instruction Manual
SEL-351-5, -6, -7 Relay
Standard Event Reports, Sag/Swell/Interruption Report, and SER
Sag/Swell/Interruption (SSI) Report (Available in Firmware Version 7)
(Continued from previous page)
14 12/05/00 16:21:12.723 20 14 29 12 0 98 98 98 0 15.29 ... E
13 12/05/00 16:21:12.727 20 14 28 12 0 98 98 98 0 15.29 ... E
12 12/05/00 16:21:12.731 20 15 28 12 0 98 98 98 0 15.29 ... E
11 12/05/00 16:21:12.735 20 15 29 12 0 98 98 98 0 15.29 ... E
10 12/05/00 16:21:12.739 20 14 29 12 0 98 98 98 0 15.29 ... E
9 12/05/00 16:21:12.743 20 14 28 12 0 98 98 98 0 15.29 ... E
8 12/05/00 16:21:12.748 20 15 28 12 0 98 98 98 0 15.29 ... E
7 12/05/00 16:21:12.752 19 15 28 12 0 98 98 98 0 15.29 ... E
6 12/05/00 16:21:12.756 19 14 28 12 0 98 98 98 0 15.29 ... E
5 12/05/00 16:21:12.760 20 14 28 12 0 98 98 98 0 15.29 ... E
4 12/05/00 16:21:12.764 20 15 28 12 0 98 98 98 0 15.29 ... E
3 12/05/00 16:21:12.768 19 15 28 12 0 98 98 98 0 15.29 ... E
2 12/05/00 16:21:12.773 19 14 29 12 0 98 98 98 0 15.29 ... E
1 12/05/00 16:21:12.777 20 14 28 12 0 98 98 98 0 15.29 ... E
Figure 12.8
Example Sag/Swell/Interruption (SSI) Report (PTCONN = WYE)
The Sag/Swell/Interruption (SSI) report in
shows the format of
the SSI report headings when the relay is configured for delta-connected PTs
(global setting PTCONN = DELTA). In this case, the
Ph ABC
column
represents the Relay Word bits as shown on the right-hand side of
.
Note that the voltage column headings are now
Vab
,
Vbc
, and
Vca
, and that the
Vbase value is scaled by
√
3 to account for the phase-to-phase quantities (as
=>
SSI 32 36 <Enter>
FEEDER A27 Date: 02/06/02 Time: 09:12:07.369
CROWN SUB
FID=SEL-351-7-R3xx-V0-Zxxxxxx-D2002xxxx CID=xxxx
I nom. A B C G = 5 Amp N = 5 Amp
Current(% I nom.) Voltage(% Vbase) Vbase Ph ST
# Date Time Ia Ib Ic Ig In Vab Vbc Vca Vs (kV) ABC
36 11/22/00 08:47:24.272 11 13 15 3 0 100 99 100 0 25.88 ... R
35 12/05/00 16:21:12.635 20 23 28 7 0 98 98 98 0 26.48 ... P
34 12/05/00 16:21:12.639 20 22 29 8 0 98 98 98 0 26.48 ... P
33 12/05/00 16:21:12.644 20 22 28 7 0 98 98 98 0 26.48 ... P
32 12/05/00 16:21:12.648 20 23 28 7 0 98 98 98 0 26.48 ... P
=>
Figure 12.9
Example Sag/Swell/Interruption (SSI) Report (PTCONN =
DELTA)
Using the SSI
Recorder on
Ungrounded/High-
Impedance Grounded
and Petersen Coil
Systems
In ungrounded/high-impedance grounded and Petersen Coil systems, the loss
of one phase voltage (caused by a phase-to-ground fault) does not affect the
delivery of power to the phase-to-phase connected loads on the distribution
system. Depending on the relay PT connection (and global setting PTCONN),
the SSI Report may or may not capture data during a single-line-to-ground
fault:
If PTCONN = WYE.
the SSI Relay Word bits respond to single-phase
voltages. The SSI report treats a single-line-to-ground fault as a sag (or
interrupt) on one phase, and a swell on the other two phases (subject to the
actual settings in use, and the fault characteristics). In this situation, the SSI
Report can be used as a fault analysis tool, capturing the phase and duration of
faults that are significant enough to cause a single-phase voltage SAG
p
element to assert.
If PTCONN = DELTA.
the SSI Relay Word bits respond to phase-to-phase
voltages. The SSI report will likely not trigger during a single-line-to-ground
fault, because the phase-to-phase voltage quantities do not change materially.
In this situation, the SSI Report is strictly a power quality tool, reporting
disturbances actually experienced by the phase-to-phase connected load on
the power system.
Содержание SEL-351-5
Страница 10: ...This page intentionally left blank ...
Страница 22: ...This page intentionally left blank ...
Страница 40: ...This page intentionally left blank ...
Страница 80: ...This page intentionally left blank ...
Страница 202: ...This page intentionally left blank ...
Страница 238: ...This page intentionally left blank ...
Страница 320: ...This page intentionally left blank ...
Страница 402: ...This page intentionally left blank ...
Страница 436: ...This page intentionally left blank ...
Страница 478: ...This page intentionally left blank ...
Страница 500: ...This page intentionally left blank ...
Страница 594: ...This page intentionally left blank ...
Страница 598: ...This page intentionally left blank ...
Страница 622: ...This page intentionally left blank ...
Страница 644: ...This page intentionally left blank ...
Страница 674: ...This page intentionally left blank ...
Страница 676: ...This page intentionally left blank ...