1.14
SEL-351-5, -6, -7 Relay
Instruction Manual
Date Code 20070117
Introduction and Specifications
Specifications
Breaking Capacity (10000 operations):
24 V
10 A
L/R = 40 ms
48 V
10 A
L/R = 40 ms
125 V
10 A
L/R = 40 ms
250 V
10 A
L/R = 20 ms
Cyclic Capacity (4 cycles in 1 second, followed by 2 minutes
idle for thermal dissipation):
24 V
10 A
L/R = 40 ms
48 V
10 A
L/R = 40 ms
125 V
10 A
L/R = 40 ms
250 V
10 A
L/R = 20 ms
Note:
Make per IEEE C37.90-1989.
Note:
Do not use high-current interrupting output contacts to
switch ac control signals. These outputs are polarity dependent.
Note:
Breaking and Cyclic Capacity per IEC 60255-0-20:1974.
Optoisolated Input Ratings
When used with dc control signals:
250 Vdc:
on for 200–300 Vdc;
off below 150 Vdc
220 Vdc:
on for 176–264 Vdc;
off below 132 Vdc
125 Vdc:
on for 105–150 Vdc;
off below 75 Vdc
110 Vdc:
on for 88–132 Vdc;
off below 66 Vdc
48 Vdc:
on for 38.4–60 Vdc;
off below 28.8 Vdc
24 Vdc:
on for 15–30 Vdc
When used with ac control signals:
250 Vdc:
on for 170.6–300 Vac;
off below 106.0 Vac
220 Vdc:
on for 150.3–264.0 Vac; off below 93.2 Vac
125 Vdc:
on for 89.6–150.0 Vac;
off below 53.0 Vac
110 Vdc:
on for 75.1–132.0 Vac;
off below 46.6 Vac
48 Vdc:
on for 32.8–60.0 Vac;
off below 20.3 Vac
24 Vdc:
on for 12.8–30.0 Vac
Note:
AC mode is selectable for each input via Global settings
IN101D–IN106D; IN201D–IN208D. AC input recognition delay
from time of switching: 0.75 cycles maximum pickup;
1.25 cycles maximum dropout.
Note:
24, 48, 125, 220, and 250 Vdc optoisolated inputs draw
approximately 5 mA of current, 110 Vdc inputs draw
approximately 8 mA of current. All current ratings are at nominal
input voltages.
Time-Code Input
Relay accepts demodulated IRIG-B time-code input at Port 1 or
Port 2.
Synchronization (specification is with respect to the accuracy
of the time source)
Synchrophasor:
±10
μ
s
Other:
±5 ms
Communications Ports
EIA-232:
1 front, 2 rear
EIA-485:
1 rear with 2100 Vdc of isolation
Per Port Baud Rate
Selections:
300, 1200, 2400, 4800, 9600, 19200,
38400 (38400 is not available on
PORT 1
)
Dimensions
Weight
13 lbs (5.92 kg)—2U rack unit height relay
16 lbs (7.24 kg)—3U rack unit height relay
Operating Temperature
–40
°
to +185
°
F (–40
°
to +85
°
C)
(LCD contrast impaired for temperatures below –20ºC.)
Type Tests
Environmental Tests
Cold:
IEC 60068-2-1:1990 Basic
Environmental testing procedures,
Part 2: Tests – Test Ad: Cold
Damp Heat Cyclic:
IEC 60068-2-30:1980 Basic
environmental testing procedures,
Part 2: Tests, Test Db and guidance:
Damp heat, cyclic (12 + 12-hour
cycle), (six-day type test)
IEC 60529:1989 [EN 60529–1992]
Degrees of Protection Provided by
Enclosures (IP code): Object
penetration and dust ingress, IP30 for
category 2 equipment.
Dry Heat:
IEC 60068-2-2:1974 Basic
environmental testing procedures,
Part 2: Tests – Test Bd: Dry Heat
Routine Dielectric and Impulse Tests
Current inputs,
optoisolated inputs,
and output contacts:
2500 Vac for 10 s
Power supply:
3100 Vdc for 10 s
IEC 60255-5 Dielectric Tests:1977
2500 Vac for 2 seconds on analog
inputs, optoisolated inputs, and
output contacts
3100 Vdc for 2 seconds on power
supply
Impulse:
IEC 60255-5:1977 Electrical relays,
Part 5: Insulation tests for electrical
relays, Section 6: Dielectric Tests,
Series C (2500 Vac on analog inputs;
3000 Vdc on power supply, contact
inputs, and contact outputs).
Section 8: Impulse Voltage Tests,
0.5 Joule 5 kV
Electrostatic Discharge Test
ESD:
IEC 60255-22-2:1996 Electrical
disturbance tests for measuring relays
and protective equipment, Section 2:
Electrostatic discharge tests, Severity
Level 4 (8 kV contact discharge all
points except serial ports, 15 kV air
discharge to all other points)
RFI and Interference Tests
Surge Withstand:
IEEE C37.90.1-1989 IEEE SWC Tests
for Protective Relays and Relay
Systems (3 kV oscillatory, 5 kV fast
transient)
Fast Transient
Disturbance:
IEC 60255-22-4:1992 Electrical
disturbance tests for measuring relays
and protection equipment, Section 4:
Fast transient disturbance test,
Severity Level 4 kV at 2.5 kHz and
5 kHz
Содержание SEL-351-5
Страница 10: ...This page intentionally left blank ...
Страница 22: ...This page intentionally left blank ...
Страница 40: ...This page intentionally left blank ...
Страница 80: ...This page intentionally left blank ...
Страница 202: ...This page intentionally left blank ...
Страница 238: ...This page intentionally left blank ...
Страница 320: ...This page intentionally left blank ...
Страница 402: ...This page intentionally left blank ...
Страница 436: ...This page intentionally left blank ...
Страница 478: ...This page intentionally left blank ...
Страница 500: ...This page intentionally left blank ...
Страница 594: ...This page intentionally left blank ...
Страница 598: ...This page intentionally left blank ...
Страница 622: ...This page intentionally left blank ...
Страница 644: ...This page intentionally left blank ...
Страница 674: ...This page intentionally left blank ...
Страница 676: ...This page intentionally left blank ...