2.11
Date Code 20070117
Instruction Manual
SEL-351-5, -6, -7 Relay
Installation
Making Rear-Panel Connections
Models 0351x1 and 0351xY
Models 0351
x
1 and 0351
x
Y have output contacts on the:
➤
main board
OUT101
–
ALARM
(ordered as standard output contacts only)
➤
extra I/O board
OUT201
–
OUT212
[ordered as standard or high-current
interrupting output contacts (all of one type or the other)]
Refer to the Specifications subsection
for output contact
ratings. To determine the type of output contacts on the extra I/O board of
your Model 0351
x
1 relay, refer to the part number on the serial number sticker
on the relay rear panel.
Standard Output Contacts
Models 0351
x
1 and 0351
x
Y part numbers with a numeral “2” in the field in
bold below (sample part numbers) indicate standard output contacts on the
extra I/O board (
OUT201
–
OUT212
):
0351
x
1H4254
2
X1
0351
x
YH4254
2
X1
Standard output contacts are not polarity dependent.
High-Current Interrupting Output Contacts
Models 0351
x
1 and 0351
x
Y part numbers with a numeral “6” in the field in
bold below (sample part numbers) indicate high-current interrupting output
contacts on the extra I/O board (
OUT201
–
OUT212
):
0351
x
1H4254
6
X1
0351
x
YH4254
6
X1
High-current interrupting output contacts are polarity dependent. Note the
+
polarity markings above even-numbered terminals
B02
,
B04
,
B06
, ...,
B24
in
. The extra I/O board of the Model 0351
x
1 relay in
does
not show these
+
polarity markings (because it is the rear panel for an extra
I/O board with standard output contacts).
As an example, consider the connection of terminals
B01
and
B02
(high-current
interrupting output contact
OUT201
) in a circuit:
Terminal
B02 (+)
has to be at a higher voltage potential than terminal
B01
in the
circuit.
The same holds true for output contacts
OUT202
–
OUT212
(if they are also high-
current interrupting output contacts).
Optoisolated Inputs
The optoisolated inputs in any of the SEL-351 models (e.g.,
IN102
,
IN207
) are
not polarity dependent. With nominal control voltage applied, each
optoisolated input draws approximately 4 mA of current. Refer to the
Specifications subsection
for optoisolated input ratings.
Inputs can be configured to respond to ac or dc control signals via Global
settings IN101D–IN106D and IN201D–IN208D.
NOTE:
Do not use the high-current
interrupting output contacts to switch
ac control signals.
Содержание SEL-351-5
Страница 10: ...This page intentionally left blank ...
Страница 22: ...This page intentionally left blank ...
Страница 40: ...This page intentionally left blank ...
Страница 80: ...This page intentionally left blank ...
Страница 202: ...This page intentionally left blank ...
Страница 238: ...This page intentionally left blank ...
Страница 320: ...This page intentionally left blank ...
Страница 402: ...This page intentionally left blank ...
Страница 436: ...This page intentionally left blank ...
Страница 478: ...This page intentionally left blank ...
Страница 500: ...This page intentionally left blank ...
Страница 594: ...This page intentionally left blank ...
Страница 598: ...This page intentionally left blank ...
Страница 622: ...This page intentionally left blank ...
Страница 644: ...This page intentionally left blank ...
Страница 674: ...This page intentionally left blank ...
Страница 676: ...This page intentionally left blank ...