7.41
Date Code 20070117
Instruction Manual
SEL-351-5, -6, -7 Relay
Inputs, Outputs, Timers, and Other Control Logic
Rotating Default Display
Reclosing Relay Disabled
, optoisolated input
IN102
is de-energized to disable the
reclosing relay, resulting in:
DP1 =
IN102
= logical 0
This results in the display of corresponding text setting DP1_0 on the front-
panel display:
Now the active setting group is switched from setting Group 1 to 4.
Switch to Setting Group 4 as the Active Setting Group
When setting Group 4 is the active setting group, the reclosing relay is always
disabled and optoisolated input
IN102
has no control over the reclosing relay.
The text settings cannot be changed (they are used in all setting groups), but
the SEL
OGIC
control equation settings can be changed:
SEL
OGIC
control equation settings:
79DTL =
1
(set directly to logical 1—reclosing relay permanently “driven-
to-lockout”)
DP1 =
0
(set directly to logical 0)
Text settings (remain the same for all setting groups):
DP1_1 =
79 ENABLED
(displayed when DP1 = logical 1)
DP1_0 =
79 DISABLED
(displayed when DP1 = logical 0)
Because SEL
OGIC
control equation display point setting DP1 is always at
logical 0, the corresponding text setting DP1_0 continually displays in the
rotating default displays:
Additional Rotating
Default Display
Example
See
and accompanying text in
Section 5: Trip and Target Logic
for an example of resetting a rotating default display with the
{TARGET RESET}
pushbutton.
Displaying Values
(other than user-
entered text) on the
Rotating Default
Display
through
list all the available values (other than the user-
entered text values, discussed previously) that rotate on the default display,
subject to the number of available display points. These available values cover
metering (
), breaker wear monitor (
), and time-overcurrent
element pickups (
).
79 ENABLED
79 DISABLED
79 DISABLED
Содержание SEL-351-5
Страница 10: ...This page intentionally left blank ...
Страница 22: ...This page intentionally left blank ...
Страница 40: ...This page intentionally left blank ...
Страница 80: ...This page intentionally left blank ...
Страница 202: ...This page intentionally left blank ...
Страница 238: ...This page intentionally left blank ...
Страница 320: ...This page intentionally left blank ...
Страница 402: ...This page intentionally left blank ...
Страница 436: ...This page intentionally left blank ...
Страница 478: ...This page intentionally left blank ...
Страница 500: ...This page intentionally left blank ...
Страница 594: ...This page intentionally left blank ...
Страница 598: ...This page intentionally left blank ...
Страница 622: ...This page intentionally left blank ...
Страница 644: ...This page intentionally left blank ...
Страница 674: ...This page intentionally left blank ...
Страница 676: ...This page intentionally left blank ...