3.19
Date Code 20070117
Instruction Manual
SEL-351-5, -6, -7 Relay
Overcurrent, Voltage, Synchronism Check, Frequency, and Power Elements
Time-Overcurrent Elements
Any time current I
P
goes above pickup setting 51PP and the phase time-
overcurrent element starts timing, Relay Word bit 51PR (reset indication) =
logical 0. If the phase time-overcurrent element times out on its curve, Relay
Word bit 51PT (curve time-out indication) = logical 1.
Setting 51PRS = Y
If electromechanical reset timing setting 51PRS = Y, the phase time-
overcurrent element reset timing emulates electromechanical reset timing. If
maximum phase current, I
P
, goes above pickup setting 51PP (element is
timing or already timed out) and then current I
P
goes below 51PP, the element
starts to time to reset, emulating electromechanical reset timing. Relay Word
bit 51PR (resetting indication) = logical 1 when the element is fully reset.
Setting 51PRS = N
If reset timing setting 51PRS = N, element 51PT reset timing is a one-cycle
dropout. If current I
P
goes above pickup setting 51PP (element is timing or
already timed out) and then current I
P
goes below pickup setting 51PP, there is
a one-cycle delay before the element fully resets. Relay Word bit 51PR (reset
indication) = logical 1 when the element is fully reset.
Operation of Single-Phase Time-Overcurrent Elements (51AT, 51BT, 51CT)
To understand the operation of
, and
follow the explanation given for
, substituting phase current I
A
(or I
B
or I
C
) for
maximum phase current I
P
and substituting like settings and Relay Word bits.
The settings ranges and accuracies for the single-phase time-overcurrent
elements settings are the same as the corresponding settings in
.
q
Figure 3.15
A-Phase Time-Overcurrent Element 51AT (With Directional
Control Option)
51AP
I
A
Setting
51ATC
Torque Control Switch
Directional Control
(asserted to logical 1
continuously if E32 = N)
q
(Level 1)
SEL
OGIC
Torque Control
51AT A-Phase
Time-Overcurrent Element
Curve Timing and Reset Timing
Settings
51AP
Pickup
51AC
Curve
Type
51ATD
Time
Dial
51ARS
Electromechanical
Reset? (Y/N)
Pickup
Curve
Timeout
Reset
51A
51AR
51AT
Torque
Control
TCA State
Switch Position
Logical 1
Closed
Logical 0
Open
Logic Point TCA Controls the Torque Control Switch
Setting
51ARS =
Reset Timing
Y
Electromechanical
N
1
Cycle
TCA
Relay
Word
Bits
SEL
OGIC
Setting
Содержание SEL-351-5
Страница 10: ...This page intentionally left blank ...
Страница 22: ...This page intentionally left blank ...
Страница 40: ...This page intentionally left blank ...
Страница 80: ...This page intentionally left blank ...
Страница 202: ...This page intentionally left blank ...
Страница 238: ...This page intentionally left blank ...
Страница 320: ...This page intentionally left blank ...
Страница 402: ...This page intentionally left blank ...
Страница 436: ...This page intentionally left blank ...
Страница 478: ...This page intentionally left blank ...
Страница 500: ...This page intentionally left blank ...
Страница 594: ...This page intentionally left blank ...
Страница 598: ...This page intentionally left blank ...
Страница 622: ...This page intentionally left blank ...
Страница 644: ...This page intentionally left blank ...
Страница 674: ...This page intentionally left blank ...
Страница 676: ...This page intentionally left blank ...