7-42
Inputs, Outputs, Timers, and Other Control Logic
Date Code 20010625
SEL-311L Instruction Manual
ALARM Output Contact and 87HWAL
Refer to Figure 7.26 and
Relay Self-Tests
in
Section 13: Testing, Troubleshooting, and
Commissioning
.
When the relay is operational, the alarm logic/circuitry keeps the ALARM output contact coil
energized. Depending on the ALARM output contact type (a or b), the ALARM output contact
closes or opens as demonstrated in Figure 7.26. An “a” type output contact is open when the
output contact coil is deenergized and closed when the output contact coil is energized. A “b”
type output contact is closed when the output contact coil is deenergized and open when the
output contact coil is energized.
The Relay Word bit ALARM is deasserted to logical 0 when the relay is operational. When the
relay enters Access Level 2, the ALARM Relay Word bit momentarily asserts to logical 1 (and
the ALARM output contact coil is deenergized momentarily).
To verify ALARM output contact mechanical integrity, execute the serial port command
PULSE
ALARM
. Execution of this command momentarily deenergizes the ALARM output contact
coil.
Notice in Figure 7.26 that all possible combinations of ALARM output contact coil states
(energized or deenergized) and output contact types (a or b) are demonstrated. See
Output
Contact Jumpers
in
Section 2: Installation
for output contact type options.
Contact output OUT107 can be configured in one of the following ways:
v
Use it as a regular contact similar to OUT101 through OUT106 by placing jumper
JMP23 in position 2–3.
v
Use it as an extra relay alarm by placing jumper JMP23 in position 1–2.
v
Use it as an alarm contact for the 87L hardware by placing jumper JMP23 in position 2–
3 and setting OUT107 = 87HWAL. This is how OUT107 is configured in a standard
relay shipment. Configured this way, Relay Word bit 87HWAL asserts and contact
OUT107 closes when an internal problem occurs in the 87L hardware that prevents the
relay from performing line current differential protection. (Other Relay Word bits
assert for communications channel failures.) It is also possible to configure contact
OUT107 as a normally closed alarm contact and set OUT107 = !87HWAL so that loss
of control power also closes contact OUT107.
R
OTATING
D
EFAULT
D
ISPLAY
The rotating default display on the relay front panel replaces indicating panel lights. Traditional
indicating panel lights are turned on and off by circuit breaker auxiliary contacts, front-panel
switches, SCADA contacts, etc. They indicate such conditions as:
circuit breaker open/closed
reclosing relay enabled/disabled
Содержание SEL-311L
Страница 6: ......
Страница 8: ......
Страница 26: ......
Страница 54: ......
Страница 144: ......
Страница 203: ...Date Code 20010625 Trip and Target Logic 5 27 SEL 311L Instruction Manual Figure 5 12 DCUB Logic ...
Страница 216: ......
Страница 252: ......
Страница 302: ......
Страница 338: ......
Страница 480: ......
Страница 484: ......
Страница 486: ......
Страница 502: ......
Страница 532: ...12 28 Standard Event Reports and SER Date Code 20010625 SEL 311L Instruction Manual 4 ...
Страница 552: ......
Страница 554: ......
Страница 574: ......
Страница 576: ......
Страница 596: ......
Страница 602: ......
Страница 628: ......
Страница 656: ......
Страница 662: ......
Страница 664: ......
Страница 688: ......
Страница 700: ......
Страница 716: ......
Страница 722: ......
Страница 734: ......