Inputs, Outputs, Timers, and Other Control Logic
Date Code 20010625
SEL-311L Instruction Manual
Figure 7.26: Logic Flow for Example Output Contact Operation
High-Speed Output Contacts OUT201 Through OUT206
The SEL-311L Relay contains six special high-speed contacts, OUT201 through OUT206,
intended for use as trip contacts by the line current differential protection. These contacts close
less than 10 microseconds after their control coil is energized via setting EHST. OUT201
through OUT206 are rated to interrupt trip current, which helps avoid the added delay caused by
tripping auxiliary relays.