Date Code 20010625
Standard Event Reports and SER
12-1
SEL-311L Instruction Manual
SECTION 12: STANDARD EVENT REPORTS AND SER
I
NTRODUCTION
The SEL-311L Relay provides two separate event reports:
v
Standard 15/30/60-cycle oscillographic event reports for backup protection.
v
Standard 15/30/60-cycle oscillographic event reports for line current differential
protection.
In addition, the SEL-311L Relay also provides Sequential Events Recorder (SER) reports.
The standard event reports contain date, time, current, voltage, frequency, relay element,
optoisolated input, output contact, and fault location information.
The relay generates (triggers) line current differential and backup protection 15/30/60-cycle
event reports simultaneously by both fixed and programmable conditions. These reports show
information for 15, 30, or 60 continuous cycles. At least forty-one 15-cycle, twenty-two 30-
cycle, or eleven 60-cycle reports are maintained for both backup and line current differential
protection. If more reports are triggered, the latest event report overwrites the oldest event
report. See Figure 12.4 for an example standard 15-cycle backup event report and Figure 12.5
for an example standard 15-cycle differential event report.
The relay adds lines in the sequential events recorder (SER) report for a change of state of a
programmable condition. The SER lists date and time-stamped lines of information each time a
programmed condition changes state. The relay stores the latest 512 lines of the SER report in
nonvolatile memory. If the report fills up, newer rows overwrite the oldest rows in the report.
See Figure 12.8 for an example SER report.
S
TANDARD
15/30/60-C
YCLE
E
VENT
R
EPORTS
See Figure 12.4 and Figure 12.5 for example event reports (
Note
are on multiple pages).
Event Report Length (Settings LER and PRE)
The SEL-311L Relay provides user-programmable event report length and pre-fault length.
Event report length is 15, 30, or 60 cycles. Pre-fault length ranges from 1 to 59 cycles. Pre-fault
length is the first part of the event report that precedes the event report triggering point.
Set the event report length with the
SET G LER
setting. Set the pre-fault length with the
SET
G PRE
setting. See the
SET G
command in Table 9.1 and corresponding Settings Sheets in
Section 9: Setting the Relay
for instructions on setting the LER and PRE settings.
Changing the LER setting erases all events stored in nonvolatile memory. Changing the PRE
setting has no effect on the nonvolatile reports.
Содержание SEL-311L
Страница 6: ......
Страница 8: ......
Страница 26: ......
Страница 54: ......
Страница 144: ......
Страница 203: ...Date Code 20010625 Trip and Target Logic 5 27 SEL 311L Instruction Manual Figure 5 12 DCUB Logic ...
Страница 216: ......
Страница 252: ......
Страница 302: ......
Страница 338: ......
Страница 480: ......
Страница 484: ......
Страница 486: ......
Страница 502: ......
Страница 532: ...12 28 Standard Event Reports and SER Date Code 20010625 SEL 311L Instruction Manual 4 ...
Страница 552: ......
Страница 554: ......
Страница 574: ......
Страница 576: ......
Страница 596: ......
Страница 602: ......
Страница 628: ......
Страница 656: ......
Страница 662: ......
Страница 664: ......
Страница 688: ......
Страница 700: ......
Страница 716: ......
Страница 722: ......
Страница 734: ......