5-26
Trip and Target Logic
Date Code 20010625
SEL-311L Instruction Manual
Logic Outputs
The following logic outputs can be tested by assigning them to output contacts. See
Output
Contacts
in
Section 7: Inputs, Outputs, Timers, and Other Control Logic
for more information
on output contacts.
UBB1, UBB2—Unblocking Block Output(s)
In two-terminal line DCUB applications (setting ECOMM = DCUB1), UBB1 disables tripping if
the loss-of-channel condition continues for longer than time UBDURD.
In three-terminal line DCUB applications (setting ECOMM = DCUB2), UBB1 or UBB2 disable
tripping if the loss-of-channel condition (for the respective Channel 1 or 2) continues for longer
than time UBDURD.
The UBB1 and UBB2 are routed in various combinations in Figure 5.13 to control Relay Word
bit UBB, depending on enable setting ECOMM = DCUB1 or DCUB2. Relay Word bit UBB is
the unblock block input into the trip logic in Figure 5.4. When UBB asserts to logical 1, tripping
is blocked.
Содержание SEL-311L
Страница 6: ......
Страница 8: ......
Страница 26: ......
Страница 54: ......
Страница 144: ......
Страница 203: ...Date Code 20010625 Trip and Target Logic 5 27 SEL 311L Instruction Manual Figure 5 12 DCUB Logic ...
Страница 216: ......
Страница 252: ......
Страница 302: ......
Страница 338: ......
Страница 480: ......
Страница 484: ......
Страница 486: ......
Страница 502: ......
Страница 532: ...12 28 Standard Event Reports and SER Date Code 20010625 SEL 311L Instruction Manual 4 ...
Страница 552: ......
Страница 554: ......
Страница 574: ......
Страница 576: ......
Страница 596: ......
Страница 602: ......
Страница 628: ......
Страница 656: ......
Страница 662: ......
Страница 664: ......
Страница 688: ......
Страница 700: ......
Страница 716: ......
Страница 722: ......
Страница 734: ......