System Does Not Respond to Commands
Communications device not connected to system.
Relay or communications device at incorrect baud rate or other communication parameter
incompatibility, including cabling error.
Internal connector loose or disconnected.
System is currently processing event record (wait several seconds).
System is attempting to transmit information, but cannot due to handshake line conflict
(check communications cabling).
System is in the XOFF state, halting communications (type
<CONTROL> Q
to put
system in XON state).
Tripping Output Relay Remains Closed Following Fault
Tripping condition still present.
Output relay contacts burned closed.
Failure of main board.
No Prompting Message Issued to Terminal upon Power-Up
Terminal not connected to system.
Wrong baud rate.
Improper connection of terminal to system.
Other port designated as the AUTOMATIC port (see AUTO setting in the SET com-
mand).
Failure of main board.
Port timeout interval set to a value other than zero.
6-10
Maintenance and Testing
SEL-267D/167D Instruction Manual
Date Code 940208
Содержание SEL-167D
Страница 3: ......
Страница 6: ......
Страница 8: ......
Страница 9: ......
Страница 10: ......
Страница 11: ......
Страница 51: ...LOGIC DIAGRAMS Date Code 920326 Specifications SEL 267D 167D Instruction Manual 2 31 ...
Страница 52: ...Date Code 920326 Specifications 2 32 SEL 267D 167D Instruction Manual ...
Страница 53: ...Date Code 920326 Specifications SEL 267D 167D Instruction Manual 2 33 ...
Страница 54: ...Date Code 920326 Specifications SEL 267D 167D Instruction Manual 2 34 ...
Страница 88: ...SAMPLE EVENT REPORT ...
Страница 114: ......
Страница 115: ......