Self-Test Failure: ROM Checksum
EPROM failure (replace EPROMs).
Self-Test Failure: RAM
Failure of static RAM IC (replace RAM).
Self-Test Failure: A/D Converter
A/D converter failure.
RAM error not detected by RAM test.
Stall Relay Closed (Alarm)
Power is off.
Blown fuse.
Power supply failure.
Improper EPROMs or EPROM failure.
Main board failure.
6-12
Maintenance and Testing
SEL-267D/167D Instruction Manual
Date Code 940208