4.
Type
END <ENTER>
to complete the setting procedure. When you receive the
"
OK
(Y or N)?
"
prompt, answer
YES <ENTER>.
The ALARM contact should close for
several seconds while the relay computes internal settings, unless an alarm condition
exists (i.e. self test failure).
5.
Use SHOWSET to inspect the settings; make sure your change was accepted.
6.
Use SET and SHOWSET again to restore and check the settings.
7.
Type
LOG MTU <ENTER>.
8.
Change one bit.
9.
Complete the logic setting procedure.
10. Type
LOG MTU <ENTER>
again, and make sure the bit change is present. Restore
the setting, and use SHOWSET to check the original setting.
METER Test
This test checks the magnitude accuracy and phase balance.
1.
Connect the voltage input terminals VA, VB, and VC. Apply 50 Vac balanced from the
terminals to the test set neutral point.
2.
Connect the current inputs and apply balanced three-phase current of five amperes
through the three inputs.
3.
Use the METER command to inspect the measured voltages, currents, and power.
Voltages VA, VB, and VC should equal the applied voltage times the potential trans-
former ratio setting. With the Example 69 kV Line settings, you should obtain:
VAB = VBC = VCA = 50 x 600 x 1.732 = 51.96 kV. (±0.5%)
Similarly, currents IA, IB, and IC should equal the applied current times the current
transformer ratio. With the Example 69 kV Line settings, you should obtain:
IA = IB = IC = 5x60 = 300A. (±1%)
Difference currents IAB, IBC, and ICA should be less than 6 amperes:
IAB = IBC = ICA = 50 x 60 x 1.732 = 5.19 A
The power reading should be:
VAxIA + VBxIB + VCxIC = 27MW.
The reactive power reading should be less than 0.24 MVAR.
6-6
Maintenance and Testing
SEL-267D/167D Instruction Manual
Date Code 920326
Содержание SEL-167D
Страница 3: ......
Страница 6: ......
Страница 8: ......
Страница 9: ......
Страница 10: ......
Страница 11: ......
Страница 51: ...LOGIC DIAGRAMS Date Code 920326 Specifications SEL 267D 167D Instruction Manual 2 31 ...
Страница 52: ...Date Code 920326 Specifications 2 32 SEL 267D 167D Instruction Manual ...
Страница 53: ...Date Code 920326 Specifications SEL 267D 167D Instruction Manual 2 33 ...
Страница 54: ...Date Code 920326 Specifications SEL 267D 167D Instruction Manual 2 34 ...
Страница 88: ...SAMPLE EVENT REPORT ...
Страница 114: ......
Страница 115: ......