The following data are required to set the relay:
R1, X1
R0, X0
LL
CTR
PTR
MTA
LOCAT
DATC
DCTH
79OI1
790I2
790I3
79RS
51PP
51PTD
51PC
51PTC
50P1
50P2
50P3
Z1DP
Z2DP
Z3DP
51NP
51NTD
51NC
51NTC
Positive-sequence primary impedance of line (0-9999 ohms)
Zero-sequence primary impedance of line (0-9999 ohms)
Line length (0.1-999 miles)
CT ratio (e.g., for 600:5, enter 120) (l-5000)
PT ratio (e.g., 1200: 1, enter 1200) (l-10,000)
Maximum torque angle for directional elements (47°-90°)
Do you want to enable the fault locator for Looped, Radial, or No operation
(L, R, N)?
Demand ammeter time constant (5-60 minutes)
Demand current threshold (25-50,000 primary amperes)
Reclosing relay open interval 1 (¼ to 10,000 cycles; 0 disables reclosing for
intervals 1, 2 and 3)
Reclosing relay open interval 2 (¼ to 10,000 cycles; 0 disables reclosing for
intervals 2 and 3)
Reclosing relay open interval 3 (¼ to 10,000 cycles; 0 disables reclosing for
interval 3)
Reclosing relay reset time (60 to 8,000 cycles)
Phase time-overcurrent pickup (0.25-50,000 primary amperes)
Phase time-overcurrent time dial (0.5-15)
Phase time-overcurrent curve index. Choices are as follows:
Use 1 to select a moderately inverse curve
Use 2 to select an inverse curve
Use 3 to select a very inverse curve
Use 4 to select an extremely inverse curve
Do you want phase time-overcurrent directional torque control? (Y or N)
Zone 1 phase overcurrent element pickup (0.25-50,000 primary amperes)
Zone 2 phase overcurrent element pickup (0.25-50,000 primary amperes)
Zone 3 phase overcurrent element pickup (0.25-50,000 primary amperes)
Zone 1 delay for phase and three-phase faults (0-60 cycles in quarter cycle steps)
Zone 2 delay for phase and three-phase faults (0-2000 cycles in quarter cycle
steps)
Zone 3 delay for phase and three-phase faults (0-2000 cycles in quarter cycle
steps)
Residual time-overcurrent pickup (0.25-50,000 primary amperes)
Residual time-overcurrent time dial (0.5-15)
Residual time-overcurrent curve index. Choices are as follows:
Use 1 to select a moderately inverse curve
Use 2 to select an inverse curve
Use 3 to select a very inverse curve
Use 4 to select an extremely inverse curve
Do you want residual time-overcurrent directional torque control? (Y or N)
Date Code 920326
Commands and Serial Communication
SEL-267D/167D Instruction Manual
3-21
Содержание SEL-167D
Страница 3: ......
Страница 6: ......
Страница 8: ......
Страница 9: ......
Страница 10: ......
Страница 11: ......
Страница 51: ...LOGIC DIAGRAMS Date Code 920326 Specifications SEL 267D 167D Instruction Manual 2 31 ...
Страница 52: ...Date Code 920326 Specifications 2 32 SEL 267D 167D Instruction Manual ...
Страница 53: ...Date Code 920326 Specifications SEL 267D 167D Instruction Manual 2 33 ...
Страница 54: ...Date Code 920326 Specifications SEL 267D 167D Instruction Manual 2 34 ...
Страница 88: ...SAMPLE EVENT REPORT ...
Страница 114: ......
Страница 115: ......