Directional Element Checking
Type
TAR 2 <ENTER>
(TARGETS command) to observe Relay Word Row #2 with the
DFP
and DFG bits for testing the negative-sequence element. The DFP bit status is displayed
on the first LED from the left. The DFG bit status is displayed on the fifth LED from the
left.
The negative-sequence element may be checked as follows:
Apply VA = 30 volts, VB =0, and VC=0. This results in an applied V2 = 10 volts.
Apply IA = 3 amperes, corresponding to a negative-sequence current of one ampere.
Move the phase of the current with respect to the voltage, and observe the boundary of the
directional element at MTA ± 90º.
The current polarization is checked by turning off the voltage and applying a second current
source to the polarizing current input (IP). Use an amplitude of 3 amperes and move the
phase of IA with respect to IP. Maximum torque is at 0°, so you should observe the
boundary of the characteristic at ±90°.
Observe the DFP bit to check the positive-sequence element. Apply the following balanced
three-phase voltages to the relay:
MAGNITUDE
ANGLE
Use an amplitude of 5 amperes for IA and move the phase of IA with respect to the balanced
three-phase currents. Observe the boundary of the positive-sequence directional element at
MTA ±90°.
VA
VB
67
67
0
-120
VC
67 (volts)
120 (degrees)
Overcurrent Element Checking
Type
TARGET 1 <ENTER>
to check pickup of the 50N1, 50N2, and 50N3 residual-
overcurrent elements. The command displays Relay Word Row #1 with the overcurrent
element bits on the target LEDs.
Apply current to one phase, and observe the pickup and dropout of each element.
Check the pickup and dropout of the phase overcurrent elements in a similar manner by
typing
TARGET 1 <ENTER>
to display the 50P1, 50P2, and 50P3 bits on the LEDs.
Apply current to one phase, and observe the pickup and dropout of each element.
Check the pickup of residual time-overcurrent element (51NP) and phase time-overcurrent
element (51PP) with the 51NP and 51PP bits in Relay Word Row #l. Type
TARGET 1
Date Code 920326
Maintenance and Testing
SEL-267D/167D Instruction Manual
6-7
Содержание SEL-167D
Страница 3: ......
Страница 6: ......
Страница 8: ......
Страница 9: ......
Страница 10: ......
Страница 11: ......
Страница 51: ...LOGIC DIAGRAMS Date Code 920326 Specifications SEL 267D 167D Instruction Manual 2 31 ...
Страница 52: ...Date Code 920326 Specifications 2 32 SEL 267D 167D Instruction Manual ...
Страница 53: ...Date Code 920326 Specifications SEL 267D 167D Instruction Manual 2 33 ...
Страница 54: ...Date Code 920326 Specifications SEL 267D 167D Instruction Manual 2 34 ...
Страница 88: ...SAMPLE EVENT REPORT ...
Страница 114: ......
Страница 115: ......