Maintenance
EN-US · 30.30.01.01721 · 01 · 09/19
59 / 66
ü
The device is operated on a master with IO-Link revision 1.1 or higher.
ü
The Data storage feature in the configuration of the IO-Link port is activated.
4
Ensure that the new device is restored to the factory settings
before
it is connected to the IO-Link
master. If necessary, reset the device to factory settings, e.g. via the operating element.
ð
The device parameters are automatically mirrored in the master when the device is configured using
an IO-Link configuration tool.
ð
Changes to the parameters made in the user menu on the device or via NFC are mirrored in the mas-
ter.
Changes to the parameters made by a PLC program using a function module are
not
automatically mir-
rored in the master.
4
Manually mirroring data: After changing all the required parameters, execute ISDU write access to
the System Command parameter [0x0002] using the Force upload of parameter data into the master
command (numerical value 0x05) (see Data Dictionary).
Use the Parameterization server function of the IO-Link master to ensure that no data is lost
when switching the device.