Operating manual for the VISATRON VN2020
V2.0 12/2021 EN
Page
61
of
106
SCHALLER AUTOMATION
66440 Blieskastel / Saarland / Germany / Industriering 14 / P.O. Box 1280
Industrielle Automationstechnik GmbH & Co. KG
T
el. +49(0)6842-508
-
0
/ Fax -260 / Email: [email protected] /
www.schaller-automation.com
5.
Figure 76: Pump smoke into the measuring
head
6.
Figure 77: Wait for the Alarm LED to come on
Use the hand pump to pump the smoke
into the measuring head
The
LED ALARM
should come on within
a few seconds.
7.
Figure 78: Remove smoke tube and pump
8.
Figure 79: Screw in the screw plug
Remove the smoke tube and hand pump
from the measuring head
Check that the seal on the screw plug is
not damaged. If the seal is damaged,
replace the screw plug.
Screw the screw plug into the inspection
cover and tighten it to a torque of 15 Nm.