Analog Input Board
Load Cells
Supports up to (4) 350-Ohm load cells producing a net 87.5 Ohm load.
Excitation
Voltage
+7.5 V @ 150 mA (max)
Sensors
Leak Detect: Active-Low, logic-level input (includes 5V supply)
Analog Output Board - mA
Loop Power
Options: (Selected via on-board jumper)
•
Internal supply: 24 VDC, 1500 VDC isolation
•
External supply: Range 12-30 VDC
Loop Current
Range: 3.5 mA to 20.5 mA (28 mA maximum for 2 minutes)
Resolution: < 0.001 mA
Configuration
Options
Programmable Setpoints: User-defined, net-measurement thresholds that
define the loop’s 4 mA and 20 mA
output positions. The output current
follows a linear interpolation for all measurements that lie between the two
Setpoints.
Analog Output Board - V
Voltage Output
Range: (Selected via on-board jumper)
•
0 VDC to 5 VDC, 1500 VDC isolation
•
0 VDC to 10 VDC, 1500 VDC isolation
Resolution: < 0.0001 mV (0-5 V Range), < 0.0002 mV (0-10 V Range)
Load Resistance
2000 Ohm (nominal)
Configuration
Options
Programmable Setpoints: User-defined, net-measurement thresholds that
define the
output’s
lower and upper voltage limits. The output voltage
follows a linear interpolation for all measurements that lie between the two
Setpoints.