Figure 6: Analog Output Board - mA
4.5.1
Features:
•
Current Loop Interface
: A 2-position connector to the current loop circuit.
•
Current Loop Transmitter
: A voltage-to-current converter.
•
Selectable Internal/External Power
: A 2-position slider switch that allows user-selection of
the loop’s power source. If the text “
SCALE
” is visible beneath the slider, the
power is sourced
internally by
the AOB. If the text “
LOOP
” is visible, power is s
ourced externally by the user
’s loop
supply.
•
Flash Memory
: 2k-bit of non-volatile memory used to store calibration and configuration data.
•
16-bit DAC
: A voltage-output, Digital-to-Analog Converter.
4.6
Analog Output Board (0-5V/10V Output)
With reference to Figure 7, the AOB-V is an optional board that supports selectable 0-5V or 0-10V
output range.
Its instantaneous voltage output is linearly proportional to the measurement value’s
relative position between two user-defined limit values. External wire connections are made to the 2-
position terminal block according to
Current
Loop
Interface
Selects either
Internal (SCALE) or
External (LOOP) Power
Flash Memory
16-bit DAC
Current Loop
Transmitter