Saia-Burgess Controls AG
Manual
Manual PCD 1 / PCD 2 Series
│ Document 26
/
737 E
N22 │ 2013-11-26
5
Input/output (I/O) modules
5-26
Digital output modules
5.4.3 PCD2.A460, 16 digital outputs for 0.5 A each, with ribbon connector
Application
Low cost output module with 16 transistor outputs 5 … 500 mA, with short-circuit
protection. The individual circuits are electrically connected; the voltage range is
10 … 32 V
DC
.
Technical data
Number of outputs:
16, electrically connected
Output current:
5 … 500 mA (leakage current max. 0,1 mA)
Within the voltage range 5 … 24 V
DC
, the
load resistance should be at least 48
Ω
Short circuit protection
yes
Total current per module:
8 A on 100 % duty cycle
Operating mode:
Source operation (positive switching)
Voltage range:
10 …
32 V
DC
, smoothed, max. 10 % residual ripple
Voltage drop:
max. 0.3 V at 0.5 A
Output delay:
typically 50 µs, max. 100 µs for resistive load
Resistance to interference:
acc. to IEC 801-4
4 kV under direct coupling
2 kV under capacitive coupling (whole trunk group)
Internal current consumption:
(from +5 V bus)
max 74 mA (all outputs = “1”)
typically 40 mA
Internal current consumption:
(from V+ bus)
0 mA
External current consumption: Load current
Terminals:
34-pole ribbon cable connector
LEDs and connection terminals
Bus-Stecker
Bus-Interface
Freilaufdioden
LEDs (3-farbig)
Anschlussstecker
für Flachbandkabel
Quad Ausgangstreiber
2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33
A15
A0
A8 A7
+ + + +
+ + + +
A15
A14
A13
A12
A11
A10
A9
A8
A7
A6
A5
A4
A3
A2
A1
A0