Saia-Burgess Controls AG
Manual
Manual PCD 1 / PCD 2 Series
│ Document 26
/
737 E
N22 │ 2013-11-26
4
Communication interfaces
4-34
Profibus
4.9.1 Profibus DP Master, module PCD7.F750
PCD1.M120 / M130 and PCD2.M120 / M150
The bus should be connected directly to the PCD7.F750 Module.
5
3
2
1
0
4
DP+5V
DP GND
RxD/TxD-P
PGND
RTS
RxD/TxD-N
PCD7.F750
PCD2.M170
The bus should be connected to the D-Sub connector. The pin configuration is as per
the Profibus standard. Alternatively the Profibus
can be attached to the screw termi-
nal block.
Profibus DP Master
PCD2.M170
PCD7.F750
PCD7.F750
B2
B1
B1
B2
#0
#8
#9
PGU
39
38
37
36
35
34
33
32
31
30
39
38
37
36
34
33
40
41
42
43
44
45
46
47
48
49
43
44
46
47
48
49
Port # 9
Port
# 8
Socket
B1 Port #9
B2 Port #8
Kind of con-
nection
D-Sub
Screw terminal block D-Sub
Screw terminal block
9 pole
10 pole
9 pole
10 pole
Signal
Pin number Terminal number
Pin number Terminal number
RTS / CNTR-P
4
33
4
43
PGND
1
35
1
45
RxD / TxD-N
8
36
8
46
RxD / TxD-P
3
37
3
47
DP GND
5
38
5
48
DP +5 V
6
39