![SBC PCD1 Series Скачать руководство пользователя страница 100](http://html1.mh-extra.com/html/sbc/pcd1-series/pcd1-series_manual_1205032100.webp)
Saia-Burgess Controls AG
Manual
Manual PCD 1 / PCD 2 Series
│ Document 26
/
737 E
N22 │ 2013-11-26
4
Communication interfaces
4-12
Onboard interfaces
4.5.7
Profi S-Net on PCD2.M480
The PCD2.M480 is equipped with a Profi S-Net interface as standard. This can be
used both for programming and for communication with other CPUs (that support
Profi S-Bus) and / or SBC RIOs.
Technical details:
Transmission rates up to 1.5 MBit / s
Number of stations up to 124 stations in segments of 32 stations each
Protocols
Profi S-Bus, Profi S-IO, DP Slave, HTTP in preparation
(multi-protocol operation on the same interface)
Connection diagram
Option
B1
S-Net
MPI
PCD2.M480
B2
B1
COM
PGU
Port #10 D-Sub
Pin
Profibus DP
Master
S-Net
1
-
2
-
3
RxD / TxD-P
4
RTS / CNTR-P
5
GND
6
+5 V
7
-
8
RxD / TxD-N
9
-
For details of the configuration and programming of Profi S-Net functions, please
consult the specialised manuals.