![SBC PCD1 Series Скачать руководство пользователя страница 174](http://html1.mh-extra.com/html/sbc/pcd1-series/pcd1-series_manual_1205032174.webp)
Saia-Burgess Controls AG
Manual
Manual PCD 1 / PCD 2 Series
│ Document 26
/
737 E
N22 │ 2013-11-26
5
Input/output (I/O) modules
5-38
Digital output modules, electrically isolated
5.5.4 PCD2.A250, 8 relays with make contacts, without contact protection
Application
The module contains 8 relays with normally-open contacts for direct or alternating
current up to 2 A, 48 V
AC
. The module is especially suited wherever AC switching
circuits with infrequent switching have to be controlled. For space reasons, there is
no integrated contact protection.
Technical data
Number of outputs:
4 + 4 make contacts with common terminal
Type of relay (typical):
RE 030024, SCHRACK
Operating mode:
> 12 V, > 100 mA
Switching capacity: *)
(contact lifetime)
2 A, 48 V
AC
AC1
0.7 × 10
6
operations
1 A, 48 V
AC
AC11
1.0 × 10
6
operations
2 A, 50 V
DC
DC11
0.3 × 10
6
operations
3)
1 A, 24 V
DC
DC11
0.1 × 10
6
operations
1)3)
Relay coil supply:
2)
nominal 24 V
DC
smoothed or pulsed,
8 mA per relay coil
Voltage tolerance, dependent on
ambient temperature:
20 °C: 17.0 … 35 V
DC
30 °C: 19.5 … 35 V
DC
40 °C: 20.5 … 32 V
DC
50 °C: 21.5 … 30 V
DC
Output delay:
typically 5 ms at 24 V
DC
Resistance to interference:
acc. to IEC 801-4
4 kV under direct coupling
2 kV under capacitive coupling (whole trunk group)
Internal current consumption:
(from +5 V bus)
1 … 25 mA
typically 15 mA
Internal current consumption:
(from V+ bus)
0 mA
External current consumption:
max. 64 mA
Terminals:
Pluggable 14-pole screw terminal block
(4 405 4869 0), for wires up to 0.6 mm²
1)
With external protective diode
2)
With reverse voltage protection
3)
These ratings are not UL-listed
*)
Higher voltages are not allowed for this module because safety standards for clearance
and creepage distances do not apply.
In the appendix, Chapter A.4 relay contacts, are calculation data and wiring suggestions
for the relay contacts. These data should be absolutely considered for safe switching and a
long life span of the relays.