Saia-Burgess Controls AG
Manual
Manual PCD 1 / PCD 2 Series
│ Document 26
/
737 E
N22 │ 2013-11-26
CPUs and expansion housings
3-33
Pin Configuration PCD1
3
3.12
Pin Configuration PCD1
Situation of sockets and screw terminal blocks on PCD1
B
Profibus DP - Master/Slave
(PCD7.F750 / PCD7.F770)
LonWorks
®
(PCD7.F800)
25
20
10
19
PGU/RS-232
Port #0
Small Terminal (PCD7.D162)
A
Port #1
PCD1.M125
B
Profibus DP - Master/Slave
(PCD7.F750 / PCD7.F770)
LonWorks
®
(PCD7.F800),
Ethernet-TCP/IP (Ether-S-Bus)
(PCD7.F650),
25
20
10
19
PGU/RS-232
Port #0
Small Terminal (PCD7.D162)
A
Port #1
PCD1.M135
Small Terminal PCD7.D162
25
20
10
11
12
19
PGU/RS-232
Port #0
Port #1
PCD1.M110
RS-485
(on board)
Supply/Interrupts
Optional serial data ports, socket A, Port #1 (Screw terminal block)
Pin
20…25
Signal
Pin
10...19
RS-485
2)
PCD7.F110
RS-422
PCD7.F110
RS-232
PCD7.F120
TTY/20 mA
PCD7.F130
RS-485
3)
PCD7.F150
MP-Bus
PCD7.F180
20
+24V
10
PGND
PGND
PGND
PGND
PGND
PGND
21
+24V
11
RX-TX
TX
TXD
TS
RX-TX
MP
22
PGND
12
/RX-/TX
/TX
RXD
RS
/RX-/TX
‚MFT‘
23
PGND
13
–
RX
RTS
TA
–
‚
IN
‘
24
INB2
1
)
14
–
/RX
CTS
RA
–
‚
GND
‘
25
INB1
1
)
15
PGND
PGND
PGND
PGND
PGND
PGND
16
–
RTS
DTR
TC
–
17
–
/RTS
DSR
RC
–
18
–
CTS
RSV
TG
SGND
19
–
/CTS
DCD
RG
–
1)
Not valid for the PCD1.M110
2)
Also valid for the built-in RS-485 interface of PCD1.M110
3)
galvanically isolated
PGU/RS-232, Port #0 see table PCD2
Moduls at socket B
Profibus DP and
L
on
W
orks
®
The bus should be connected directly to the PCD7.F7x0 module.
Connection can be achieved via screw terminal blocks. For details see manuals 26/737, 26/742, 26/765,
26/767
Ethernet-TCP/IP module
Ethernet-TCP/IP as configured system PCD1.M135F655 (with special cover no. 4 104 7409 0).
Connection can be achieved via RJ 45 plug of category 5. For details see manual 26/776