Saia-Burgess Controls AG
Manual
Manual PCD 1 / PCD 2 Series
│ Document 26
/
737 E
N22 │ 2013-11-26
5
Input/output (I/O) modules
5-16
Digital input modules, electrically isolated
5.3
Digital input modules, electrically isolated
PCD2.E500
6 inputs for 115 - 230 V
AC
PCD2.E610
8 inputs 24 V
DC
,
10 ms
PCD2.E611
8 inputs 24 V
DC
, 0.2 ms
PCD2.E613
8 inputs 48 V
DC
, 9 ms
PCD2.E616
8 inputs 5 V
DC
, 0.2 ms,
Electrical isolation of outputs to the Saia PCD
®
.
The channels are not isolated from each other.
Definition of input signals
for 5 V
DC
for 24 V
DC
for 48 V
DC
PCD2.E616
PCD2.E610, PCD2E611
PCD2.E613
7 V
DC
5 V
DC
2.5 V
DC
0 V
DC
1 V
DC
-7 V
DC
1
0
30 V
DC
24 V
DC
15 V
DC
0 V
DC
5 V
DC
-30 V
DC
1
0
60 V
DC
48 V
DC
30 V
DC
0 V
DC
10 V
DC
-60 V
DC
1
0
for 115 – 230 V
AC
PCD2.E500
1
0
250 V
AC
80 V
AC
40 V
AC
0 V
AC
Installation instructions
For reasons of safety it is not permissible to connect low voltages (up to 50 V) and
higher voltages (50 … 250 V) to the same module.
If a Saia PCD
®
module is connected to a higher voltage (50 … 250 V), approved com
-
ponents for this voltage must be used for all elements that are electrically connected
to the system.
Using higher voltage (50 … 250 V), all connections to the relay contacts must be
connected on the same circuit, i.e. in such a way that they are all protected against
one AC phase by one common fuse. Each load circuit may also be protected
individually.
I/O modules and I/O terminal blocks may only be plugged in and removed when the
Saia PCD
®