6 Motor setting parameters
06-00
Motor rated current setting
Factory setting
100
Setting range 30
~
120%
This parameter must be set according to specifications on nameplate of the motor. Factory setting shall be set
according to rated current of AC motor drive. By this parameter, output current of AC motor drive shall be
controlled to prevent motor overheat.
Provided that current of motor exceeds this setting, output frequency shall
decrease until current draws below setting value.
Note:This parameter can be programmed while the drive is running.
06-01
Motor no-load current setting
Factory setting
40
Setting range 0
~
99%
This parameter sets the motor no-load current in 1% increments.
Rated current of the AC motor shall be 100%.
06-02
Torque compensation increment
Factory setting
0
Setting range 0
~
20%
This parameter may be set so that the AC drive will increase the voltage output during startup to obtain a higher
initial starting torque. This additional torque will be present until the master operating frequency is attained.
Be careful while setting the value for 06-02. If the value is too high, the motor might overheat or be damaged.
06-03
Slip compensation increment
Factory setting
0.0
Setting range 0.0
~
10.0
Since load and slip shall increase when AC motor drives induction motor, this parameter( set value:0.0-10.0) can
set compensation frequency to decrease slip and provide the motor running speed under rated current approach
synchronous rotating speed.
When output current of AC motor drive exceeds motor no load current (06-01 set value), the motor drive shall
compensate frequency in accordance with 06-03 parameter.
7
Protection Parameters
07-00
Over voltage stall prevention function setting
Factory setting
1
Setting range
0:Unavailable
1:Available
When deceleration is performed, back-up energy may be generated in AC motor drive due to inertia of motor load,
and DC side voltage may rise to max value. Thus, when over voltage stall prevention is started, over voltage at
DC side shall be detected, and deceleration shall be interrupted (output frequency shall be kept), which will not be
performed again by AC motor drive until voltage is below setting value.
It need a very short time for deceleration,
we should cancel this function, at the same time equipped with braking resistor.