21
4.
LIST OF DESCRIPTIONS FOR FUNCTIONAL PARAMETERS
00:System parameters
Set during running available * the values of different machine models are different.
Parame
ter
Parameter functions
Setting range
Factory
setting
00-00 Machine Model Recognition
Display according to machine model
Type
Setting
00-01 Rated Voltage Display
Display according to machine model
00-02
Rated Current Display
Display according to machine model
00-03 Parameter Lock/Reset Setting
0:All parameters set to read/write mode
1:All parameters set to read only mode
2
~
9:Reserved
10:All parameters reset to factory setting
0
00-04 Machine ON Display Selection
0:F (frequency reference)
1:H (output frequency)
2:U (Display multi-function contents 00-05)
3:A (output current)
4:S (FWD/REV rotation reference)
0
00-05 Determining multifunctional display
0:Displaying output voltage
1:Displaying DC-BUS voltage
2:Displaying count value
3:Displaying rotating speed
0
01:Basic Parameters
Set during running available * the values of different machine models are different.
Parame
ter
Parameter functions
Setting range
Factory
setting
01-00
Master Frequency Input Setting
0:The master frequency input is controlled
by digital exerciser
1:Reserved (panel potentiometer input)
2:Master frequency is input by analog
signals AVI1(DC0 to +10V)
3:Master frequency is input by analog
signals ACI (DC 4 to 20mA) /(DC 0 to +5V)
4:Master frequency is controlled by RS485
communication interface
5:External UP/DOWN pin control
6:Reserved
0
01-01
Operation Comman source setting
0:Operated by digital exerciser
1:Operated by external terminals. STOP on
keyboard available
2:Operated by the control keyboard of the
external terminals. STOP on keyboard
unavailable
3:Operated by Communication Interface
RS485. STOP on keyboard available
4:Operated by Communication Interface
RS485. STOP on keyboard unavailable
0
01-02
Max operation frequency setting
50.00
~
600.00 Hz
50.00