07-09 Recent 1
st
fault record
1:SC IGBT short-circuit protection
2:OU (Over voltage)
3:OC (Over current)
4:OL ( Inverter over load)
5:OH (Over heating)
6:EF (External fault)
7:OCA the acceleration current is over the
double rated current
8:OCn the constant speed current is over
the double rated current
9:OCd the deceleration current is over the
double rated current
10:CF1 (Writing EEPROM error)
11:CF2 (Reading EEPROM error)
12:CF3 (Drive internal hardware error)
13:OL2 (Motor overload)
14:PHL (Phase loss protection)
15:AUE (Automatic measurement of motor
parameters failed)
16:CODER (Code Error)
17:OL1 (Electrical thermal relay)
0
07-10 Recent 2
nd
fault record
07-11 Recent 3
rd
fault record
08:Communication Parameters
Set during running available * the values of different machine models are different.
Parame
ter
Parameter functions
Setting range
Factory
setting
08-00 Communication address
0
~
254
1
08-01 Communication transmitting speed
4.8
~
115.2 kbits/s
9.6
08-02 Transmitting fault treatment
0:Warning and running continuously
1:Warning and deceleration to stop
2:Warning and coasting to a stop
3:No warning and running continuously
3
08-03 Time out detected
0:Not detected
1
~
100 Sec
0
08-04 Communication Material Format
0:7,N,1 FOR ASCII
1:7,N,2 FOR ASCII
2:7,E,1 FOR ASCII
3:7,O,1 FOR ASCII
4:7,E,2 FOR ASCII
5:7,O,2 FOR ASCII
6:8,N,1 FOR ASCII
7:8,N,2 FOR ASCII
8:8,E,1 FOR ASCII
9:8,O,1 FOR ASCII
10:8,E,2 FOR ASCII
11:8,O,2 FOR ASCII
12:8,N,1 FOR RTU
13:8,N,2 FOR RTU
14:8,E,1 FOR RTU
15:8,O,1 FOR RTU
16:8,E,2 FOR RTU
17:8,O,2 FOR RTU
0