![Savch S200 Series Скачать руководство пользователя страница 36](http://html.mh-extra.com/html/savch/s200-series/s200-series_user-manual_1203756036.webp)
32
01-11
1
st
acceleration time setting
Factory setting
10.00
Setting range 0.10
~
400.00 Sec
The multi-function input terminal is set to be used to switch the Acc/Dec time, but in this time , It does not
work(“open”) or never to be set to this function for switching Acc/Dec time, then the AC drive will accelerate
according to the 1
st
Acc. time. This parameter is determined by the time which the AC motor drive required when
it accelerate from 0 Hz to [max. frequency] (01-
02). The rate is linear unless S Curve is “Enabled”.
01-12
1
st
deceleration time setting
Factory setting
10.00
Setting range 0.10
~
400.00 Sec
The multi-function input terminal is set to be used to switch the Acc/Dec time, but in this time , It does not
work(“open”) or never to be set to this function for switching Acc/Dec time, then the AC drive will decelerate
according to the 1st Dec. time. This parameter is determined by the time which the AC motor drive required when
it decelerate from [max. frequency] (01-
02) to 0 Hz. The rate is linear unless S Curve is “Enabled.
01-13
2
nd
acceleration time setting
Factory setting
10.00
Setting range 0.10
~
400.00 Sec
When the multi-function input terminal is set to be used to switch 1
st
and 2
nd
Acc/Dec time and can work, then
the AC drive will Accelerate according to the 2
st
Acceleration time.This parameter is determined by the time which
the AC motor drive required when it accelerate from 0 Hz to [max. frequency] (01-02). The rate is linear unless S
Curve is “Enabled”.
01-14
2
nd
deceleration time setting
Factory setting
10.00
Setting range 0.10
~
400.00 Sec