11
Wiring shall be checked whether correct or not. Peripheral wiring shall fulfill the following requirements.
(Do not use a buzzer of control circuit to check wiring)
(A)Wiring for control circuit Power supply must be isolated or far from other high voltage wirings or high
current power lines, thus electromagnetic interference can be avoided. See diagrams below:
●Individual power supply bridge for inverter
MCCB
Power
supply
S200
IM
●If inverter power supply circuit is used commonly
with other machines, inverter-specialized noise
filter or isolating transformer shall be added.
MCCB
Machine
MCCB
Power
supply
S200
Noise
filter
IM
MCCB
IM
S200
Machine
Isolated transformer
Power
suppy
●Good effect may not be received if general use
noise filters are applied
MCCB
Power
supply
IM
S200
Machine
Noise
filter in
general
use
MCCB
MCCB
Power
supply
IM
S200
Machine
Noise
filter in
general
use
MCCB
●Interference during transmission can be prohibited by adding an inverter-specialized noise filter at main
circuit output side. For preventing electromagnetic radiation, a metal tube shall be installed, and distance from
signal wiring of other control machines shall be 30cm at least
SIGNAL CABLE
IM
Above 30cm
Power
supply
MCCB
FANEL
S200
Noise
filter
Noise
filter
Control
machine