- 20 - 

draught (it might occur  smoke 
from  blowing  fan  or  the  lover 
door 

Sudden 
temperature 
and pressure 
rise

 

installation valves closed

 

open the valves

 

 

pressure vessel frozen

 

heat the pressure vessel

 

Water  licking 
out of

 

boiler 

so  called  boiler’s  sweating", 
this  is  natural  process  caused 
by  temperature  difference  in 
boiler

 

during  boiler’s  start-up  and  after 
each standby "heat the boiler" e.g. 
burn  it  up  to  70°C    and  keep  that 
temperature for several hours

 

Inappropriate 
flame picture 
on the     
combustion 
chamber 

red, smoking fire indicating to 
low air supply 

provide more air 

Pale, white fire indicates to 
high air supply 

provide less air 

very  shallow  fire  in  retort 
indicating,  that  percentage  of 
coal 

volume 

is 

too 

low 

comparing to the amount of air 
delivered 

provide  more  coal  or  less  air 
reducing blow-in power 

discarding 

glowing 

not 

completely burned off pieces of 
coal 

reduce the set of fuel supply by   5 
–  10%  or  increase  blow  in  power. 
Wait  20-30  minutes  until  such 
changes  come  to  effect,  what 
should  be  deflected  in  change  of 
fire state 

 

 

 

In  order  to  ensure  the  failure-free  and  safe  operation  (to  maximum  extent)  the  
controller  of  boiler  is provided with  many  protection  functions. If faulty  status  is  
discovered,  the    alarm    is  launched    (acoustic  signal),  and  a  message  is  shown  on 
display (depending on controller version).

 

 

THERMAL PROTECTION

 

 

The  controller  is  equipped  with  safety  temperature  limiter,  preserving  the  boiler  against  
overheating 

(boiling water in installation), if  the controller  is  damaged.  Temperature 

limiter  makes up mechanical protection measure, which is bimetallic sensor  (placed  
at the boiler water temperature sensor) cutting off  power  supply  to  blow-in  fan  and  
fuel  feeder,  if  temperature  is  higher  than  90°C   (pump still working).

 

 

TEMEPERATURE PROTECTION

 

 

The  controller  is  equipped  with  additional  temperature  protection  (electronic  
one),  for  the  case  of bimetallic sensor is faulty.  If  temperature of 95°C is  

7.  PROTECTION MEANS 

 

Содержание MULTI Series

Страница 1: ...M E T A L O W O K O T L A R S K I 28 100 Busko Zdr j Owczary ul Przemys owa 3 Phone 48 41 378 46 19 Fax 48 41 370 83 10 TECHNICAL START UP DOCUMENTATION of water boilers for heating installations SAS...

Страница 2: ...tallation 15 6 Operation and exploitation guidelines 16 6 1 Filling with water 16 6 2 Firing up and functioning of a boiler 16 6 2 1 Firing up and functioning of a boiler in automatic mode 17 6 2 2 Fi...

Страница 3: ...3...

Страница 4: ...ater temperature does not exceed 85 C and working pressure does not exceed 1 5 bar Required gases draught pressure after a boiler is 0 30 0 45 mbar depending on boiler s power These boilers may also w...

Страница 5: ...in the temperature set on the controller The controller constantly measures the temperature of water boiler Depending on the results it controls fuel feeder and ventilator At the same time the control...

Страница 6: ...arge cleaning door pos 6 furnace door pos 11 and ash box door pos 13 are placed on the boiler s front For periodic cleaning operations and also for firing up a boiler the retort may be accessed throug...

Страница 7: ...1200 1280 A1 mm 290 290 305 305 330 330 B mm 1110 1235 1235 1300 1300 1300 B1 mm 450 535 535 605 605 605 H mm 1430 1430 1490 1490 1590 1590 H1 mm 1300 1300 1375 1375 1475 1475 H2 mm 980 980 1050 1050...

Страница 8: ...door 14 air intake dosage flap 15 air draft regulator 16 connecting strip 17 hot water connector pipe 18 upper washout hole cover 19 smoke conduit clearing hole 20 smoke throttle 21 smoke conduit 22...

Страница 9: ...tent to 10 Ash melting temperature 1150 C Low coal swelling coal should not tend to stick when burner Volatile particles content 30 40 It is recommended to use coal which is prone to agglomeration cok...

Страница 10: ...allation shall be installed must conform the requirements of detailed regulations being in force at the country of destination e g PN 87 B 02411 In particular the following requirements shall be fulfi...

Страница 11: ...k draught may also cause or help in carbon black forming which is then settling down on the boiler s convection channels If the draught is too strong it will cause excessive air to draw into the retor...

Страница 12: ...system provided with three or four pass valve The main advantage of such connection is boiler protection function against low temperature corrosion preventing it from premature wear If not satisfacto...

Страница 13: ...d down 6 2 FIRING UP AND OPERATE A BOILER Before fuel fire up it is mandatory to check installation filling with water Water can t be frozen It must be checked also if there is no water leakage on boi...

Страница 14: ...as varying fuel quality may cause the boiler to burn out If the fire is out during up phase the furnace should be cleaned and boiler s channels ventilated and the whole starting procedure must be rep...

Страница 15: ...ve At the same time the controller operates the heating system circulation pump if such is provided Heat requirement in the heat installation is varying due to changing outdoor conditions such as the...

Страница 16: ...t those adverse phenomena should go away During normal exploitation of boiler in the traditional combustion mode burning process is based on periodic refueling Single load of basic fuel is sufficient...

Страница 17: ...of burned fuel and apply cleaning and conservation of the entire boiler Pay special attention to lubricate inner partitions of combustion chamber and all movable elements with oil For the period of br...

Страница 18: ...ection channels walls disrupts proper heat transfer from the exchanger lowering this way an efficiency of device and increases fuel consumption 6 6 OPERATE AND MAINTENACE OF A FEEDER AND RETORT Feeder...

Страница 19: ...nstallation improper functioning of controller or fan adjust controller s settings up to weather conditions or quality of fuel mainly feeder operation time and fuel delivery pauses should be changed t...

Страница 20: ...oal reduce the set of fuel supply by 5 10 or increase blow in power Wait 20 30 minutes until such changes come to effect what should be deflected in change of fire state In order to ensure the failure...

Страница 21: ...arried out by authorized team Before connecting a boiler to a heating installation make check if all boiler s components are in good working condition and that the boiler is fully equipped NOTE Boiler...

Страница 22: ...on alterations made by user or other third parties will cause the warranty to be invalid 8 Application of reclamation should be addressed at manufacturer 9 Boiler replacement realized by manufacturer...

Страница 23: ...umentation however basic described properties of the product shall be maintained Any remarks and questions on boiler s SAS type exploitation shall be addressed ZAK AD METALOWO KOTLARSKI Owczary ul Prz...

Страница 24: ...24 SERVICE REPAIRS...

Страница 25: ...25 SERVICE REPAIRS...

Страница 26: ...perature boiler of SAS MULTI type installed and operated in pursuance of Technical Start Up Documentation Boiler no Heating capacity Heated surface Year of manufacture Manufacturer signature and stamp...

Отзывы: