Setting 20
The below options will allow the user to configure the specific sync-wired
protocol that it should adhere to (received from the master clock) and/or to
output data.
Press the bottom button to scroll from 1 to 9 or
d
. These numbers correspond
to different protocols, specifically:
1)
58th Minute (1) -
The clock performs an hourly correction that takes 55 seconds and occurs between
XX:58:05 and XX:59:00 of every hour. It also performs two daily corrections: one at 5:00AM and another
at 5:00PM. Each daily correction is ten relay cycles, each cycle is 95 seconds long, and the cycles begin at
5:05AM/PM, 5:07, 5:09, 5:11, 5:13, 5:15, 5:17, 5:19, 5:21, and 5:23 respectively.
2)
58th Minute (2) -
The clock performs an hourly correction that takes 60 seconds and occurs between
XX:58:00 and XX:59:00. It also performs two daily corrections: one at 5:00AM and one at 5:00PM. Each
daily correction is made of twelve relay cycles, and each cycle consists of 65 seconds on and 25 seconds
off.
3)
58th Minute (3) -
The clock performs an hourly correction that takes 60 seconds and occurs between
XX:58:00 and XX:59:00. It also performs two daily corrections: one at 5:00AM and one at 5:00PM. Each
daily correction is made of twelve relay cycles, and each cycle consists of 60 seconds on and 120 seconds
off.
4)
58th Minute (4) -
The clock performs an hourly correction that takes 55 seconds and occurs between
XX:59:05 and XX:59:00. It also performs two daily corrections: one at 5:00AM and one at 5:00PM. Each
daily correction is made of twelve relay cycles, each cycle is 55 seconds long, and the cycles begin at
5:03:05AM/PM, 5:07:05, 5:11:05, 5:15:05, 5:19:05, 5:23:05, 5:27:05, 5:31:05, 5:35:05, 5:39:05, 5:43:05,
and 5:47:05 respectively.
5)
59th Minute -
The clock performs an hourly correction that takes 8 seconds and occurs between
XX:57:54 and XX:58:02. It also performs two daily corrections: one at 5:00AM and one at 5:00PM. Each
daily correction is a single 14 second pulse which lasts from 5:57:54 to 5:58:08.
6)
National time & Rauland (1) -
The clock performs an hourly correction that takes 25 seconds and
occurs between XX:00:00 and XX:00:25. It also performs two daily corrections: one at 6:00AM and one at
6:00PM. Each daily correction is made of twenty four relay cycles consisting of 25 seconds on, followed by
35 seconds off.
7)
National Time & Rauland (2) -
The clock performs an hourly correction that takes 25 seconds
and occurs between XX:00:00 and XX:00:25. It also performs two daily corrections at 6:00:25AM and
6:00:25PM. Each daily correction is a single 24 minute pulse which lasts from 6:00:25AM/PM to 6:24:25.
8)
Rauland Digital -
The clock will reset the secondary clock to 12:00:00AM, then advance the time on
the secondary clock by one minute for every 0.5 seconds that the Digital line is shorted to ground.
9)
Once a Day Pulse -
The clock relay will close at a specific time and for an amount of time decided by
the clock circuit settings (Settings 21-24 for circuit 1, or 26-29 for circuit 2).
d)
Disable Relay -
The relay is disabled. This is the default value for this function.