Control of 3-WAY ECO-i SYSTEM
1
2
3
4
5
6
7
8
1. Main Operating Functions
1-2. Automatic Control for Heating and Cooling
Automatic Heating/Cooling Control
(1) When operation starts, heating or cooling is selected according to the set temperature and the room temperature.
Room temperature Set tempe 1
Cooling
Set temperature – 1 < Room temperature Set tempe 1
Monitoring mode (*1)
Room temperature < Set temperature – 1
Heating
*1: If the difference between the room temperature and set temperature is small when operation starts, the cooling
thermostat remains in standby status (OFF) until the temperature difference increases. When the temperature differ-
ence increases, either cooling operation or heating operation is selected. This standby status is known as “monitoring
mode.”
(2) After operation starts in the selected operating mode, the set temperature is automatically shifted by +2°C (cooling opera-
tion) or –2°C (heating operation).
Example: Temperature set on the remote controller is 20°C.
Selected operating mode
Shifted set temp.
Remote controller display
1
Cooling
22°C
20°C
2
Heating
18°C
20°C
(3) Operating mode changes (heating
cooling, cooling
heating) which occur during operation as a result of temperature
changes are handled as shown below.
Heating
cooling: Room temperature
Shifted set temperature (set tempe 2°C) + 0.5°C
Cooling
heating: Room temperature
Shifted set temperature (set temperature – 2°C) – 1.0°C
Example: Temperature set on the remote controller is 20°C.
Operating mode change
Shifted set temp.
1
Heating
Cooling
20 + 2 + 0.5 = 22.5°C or higher (*2)
2
Cooling
Heating
20 – 2 – 1.0 = 17°C or lower
*2: During heating operation when the body sensor is used, a temperature shift is applied to the intake temperature
detected by the sensor, in consideration of the difference in temperature at the top and bottom of the room. (Refer
to the “Room Temperature Control” item.) If this intake shift temperature is 4°C, then the heating
cooling change
occurs when the temperature detected by the body sensor is 26.5°C or higher.
(4) Cooling (heating) operation does not change if the room temperature changes from area C
A (or A
C) within 10
minutes after the compressor turns OFF. (Monitoring mode is excepted.)
(5) When the heating/cooling change occurs, the 4-way valve switches approximately 30 to 50 seconds after the compressor
turns ON.
Shifted set temp
Shifted set temp
Selected operating mode
Selected operating mode
Remote controller display
–2 deg
–1 deg
+1 deg
+3 deg
+2 deg
+2.5 deg
–3 deg
Thermostat
ON
ON
OFF
ON
OFF
ON
OFF
ON
ON OFF
OFF
A
B
C
Heating
Heating
Cooling
TD831143-00̲W-3WAY.indb 4
TD831143-00̲W-3WAY.indb 4
2008/12/01 10:26:20
2008/12/01 10:26:20
Содержание SPW-C0705DZH8
Страница 2: ...i ...
Страница 3: ...ii ...
Страница 52: ...2 42 MEMO ...
Страница 158: ...3 106 MEMO ...
Страница 528: ...4 370 MEMO ...
Страница 546: ...6 Electrical Data 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 Electric Wiring Diagram SPW C0705 0905 1155DZH8 1 Outdoor Unit ...
Страница 547: ...1 2 3 4 5 6 7 8 6 Electrical Data 1 2 3 4 5 6 7 8 Schematic Diagram SPW C0705 0905 1155DZH8 1 Outdoor Unit ...
Страница 548: ...6 Electrical Data 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 2 Electric Wiring Diagram SPW C1305 1405DZH8 1 Outdoor Unit ...
Страница 549: ...1 2 3 4 5 6 7 8 6 Electrical Data 1 2 3 4 5 6 7 8 Schematic Diagram SPW C1305 1405DZH8 1 Outdoor Unit ...
Страница 552: ...6 8 Electrical Data 1 2 3 4 5 6 7 8 2 Indoor Unit 1 2 Electric Wiring Diagram SPW XM075 095 125 165 185XH ...
Страница 554: ...6 10 Electrical Data 1 2 3 4 5 6 7 8 2 Indoor Unit Schematic Diagram SPW SR74 94 124 164 184 254GXH56 A B ...
Страница 555: ...6 11 Electrical Data 1 2 3 4 5 6 7 8 2 Indoor Unit 3 Electric Wiring Diagram SPW ADR74 94 124GXH56 A B ...
Страница 556: ...6 12 Electrical Data 1 2 3 4 5 6 7 8 2 Indoor Unit Schematic Diagram SPW ADR74 94 124GXH56 A B ...
Страница 558: ...6 14 Electrical Data 1 2 3 4 5 6 7 8 2 Indoor Unit Schematic Diagram SPW LDR94 124 164 184 254GXH56 A B ...
Страница 560: ...6 16 Electrical Data 1 2 3 4 5 6 7 8 2 Indoor Unit Schematic Diagram SPW KR74 94 124 164 184GXH56 A B ...
Страница 562: ...6 18 Electrical Data 1 2 3 4 5 6 7 8 2 Indoor Unit Schematic Diagram SPW KR254GXH56 A B ...
Страница 563: ...6 19 Electrical Data 1 2 3 4 5 6 7 8 2 Indoor Unit 5 3 Electric Wiring Diagram SPW K075 095 125XH ...
Страница 569: ...6 25 Electrical Data 1 2 3 4 5 6 7 8 2 Indoor Unit Schematic Diagram SPW U075 095 125 165 185 255 365 485 605XH ...
Страница 572: ...6 28 Electrical Data 1 2 3 4 5 6 7 8 2 Indoor Unit 7 4 Electric Wiring Diagram SPW US075 095 125 165 185XH ...
Страница 573: ...6 29 Electrical Data 1 2 3 4 5 6 7 8 2 Indoor Unit Schematic Diagram SPW US075 095 125 165 185XH ...
Страница 575: ...6 31 Electrical Data 1 2 3 4 5 6 7 8 2 Indoor Unit Schematic Diagram SPW DR254GXH56 A B ...
Страница 577: ...6 33 Electrical Data 1 2 3 4 5 6 7 8 2 Indoor Unit Schematic Diagram SPW DR364GXH56 A B ...
Страница 579: ...6 35 Electrical Data 1 2 3 4 5 6 7 8 2 Indoor Unit Schematic Diagram SPW DR484GXH56 A B ...
Страница 581: ...6 37 Electrical Data 1 2 3 4 5 6 7 8 2 Indoor Unit Schematic Diagram SPW DR764GXH56 A B ...
Страница 583: ...6 39 Electrical Data 1 2 3 4 5 6 7 8 2 Indoor Unit Schematic Diagram SPW DR964GXH56 A B ...
Страница 585: ...6 41 Electrical Data 1 2 3 4 5 6 7 8 2 Indoor Unit Schematic Diagram SPW FR74 94 124 164 184 254GXH56 A B ...
Страница 587: ...6 43 Electrical Data 1 2 3 4 5 6 7 8 2 Indoor Unit Schematic Diagram SPW FMR74 94 124 164 184 254GXH56 A B ...
Страница 588: ...6 44 Electrical Data 1 2 3 4 5 6 7 8 2 Indoor Unit 11 Electric Wiring Diagram SPW GU055 075 105XH ...
Страница 589: ...6 45 Electrical Data 1 2 3 4 5 6 7 8 2 Indoor Unit Schematic Diagram SPW GU055 075 105XH ...
Страница 590: ...6 46 MEMO ...
Страница 702: ...8 96 MEMO ...
Страница 703: ...SANYO Electric Co Ltd Printed in Japan 200812B DC ...