− 21 −
Insulation resistance
* Accuracies of the main unit excluding the effects of test leads on
measurements.
Rated
output
voltage
250 V
500 V
1000 V 2500 V
5000 V
Measuring
Range
0.0
-104.9 MΩ
0.0-99.9 MΩ
80-1049 MΩ
0.0-99.9 MΩ
80-999 MΩ
0.80-2.09 GΩ
0.0-99.9 MΩ
80-999 MΩ
0.80-9.99 GΩ
8.0-104.9 GΩ
0.0-99.9 MΩ
80-999 MΩ
0.80-9.99 GΩ
8.0-99.9 GΩ
80-1000 GΩ
(No accuracy
1001-1199 G)
Accuracy
±(5 %rdg + 3 dgt)
±20 %
Open-
circuit
voltage
DC 250 V
0 %-+20 %
DC 500 V
0 %-+20 %
DC 1000 V
0 %-+20 %
DC 2500 V
0 %-+20 %
DC 5000 V
0 %-+20 %
Rated
current
3 mA ±0.5 mA
Short-
circuit
current
3 mA-4 mA
Terminal voltage display (
Output Voltage monitor
)
Measurement range
Resolution
Accuracy
30-6000 V
1 V
±(5 %rdg + 10 dgt)
Note: In the insulation resistance measurement, the voltage used
in measuring resistances lower than 5000 V/1.8 MΩ, 2500 V/0.9
MΩ, 1000 V/0.36 MΩ, 500 V/0.18 MΩ or 250 V/0.09 MΩ is out
of the accuracy-guaranteed range and handled as a reference
value.
This display makes it possible to check the voltage output from the
output terminal or the discharge status of the charge accumulated
in the object measured.
To measure the voltage, use the AC/DC V function.